CDX800 DESCRIPTION
input
on terminals for high voltage of up to 350 V. It includes a bipolar
opto-element that enables processing of both input signal polarities.
For AC signal, it includes integration circuit that provides for direct
processing of 50 Hz signal. Output logical value of the measured
signal is LED-signalled on the front panel. Input circuits are protected
against short-time over-voltage by suppressors and against the long-
time one by a reverse fuse.
Insulation capacity of the galvanic part is 5000 V.
Input DC voltage 3 to 30 V
Input AC voltage 3 to 30 V rms
Input AC voltage, high voltage input 150 to 350 V
CIO REO 2
Binary
output
A single relay output. It includes a relay with a single changeover
contact. The changeover contact terminal is separate, common
contact is doubled (marked as C). The LED signals the presence
of the governing signal of the relay.
Insulation capacity of the galvanic part is 5000 V.
Maximum constant voltage 400 V rms
Maximum constant current 5 A rms
39