Operating Instructions
Insulated Conductor Rail System
SinglePowerLine Program 0813
BAL0813-0007-EN
www.conductix.com
translated document
page 57 of 108
6.4.3.4
Connect rails
The mechanical and electrical connection of the conductor rail is done by means of a connector. To allow for expansion, the distance
between the hanger clamp and connector must be
400 mm!
Requirements:
The conductor rails are mounted into the hanger clamp.
NOTE!
With fixed point mounting:
Before the conductor rails are connected to each other, the anchor clamps must first be slid
onto the conductor rails (see Section 6.4.3.6).
Anchor clamps are positioned to the right and left of a hanger clamp.
Please refer to the project-specific documents for the exact position of the anchor clamps.
NOTE!
Aluminum-stainless steel and CopperECO conductor rails use the identical connector. A mixed
installation of these two types of conductor rail is permitted.
Required tools:
◼
Open-end wrench, SW17
◼
Crosshead screwdriver
◼
Contact grease
◼
Steel brush
Work steps:
→
The connection points must have exposed metal (on contact surfaces) and be thinly coated with contact grease (Order No.:
080021).
→
Slide one insulating cap half (Pos. 1) of the connector over the rail ends (see Fig. 69).
Fig. 69: Slide one insulating cap half of the connector over the rail ends
Fig. 70: Slide the connector into the first conductor bar end through
to the stopper
1
1
1
2
1