21 | Installation and Planning
2588705_A_EN_1811_UB_IOM
UB
A
B
B
C
C
D
D
D
E
D
A
2
1
B
C
D
E
A
1
D
D
Figure 6 - Ultrasonic Blower Pack Clearance Suggestions
1. Direct-mounted blower pack
2. Remote-mounted blower pack
Table 5: Clearances for the Ultrasonic Blower Pack
Dimensions
US 7, 13, 20
(medium housing)
US 40
(large housing)
A
3.7 m (12 ft)
3.7 m (12 ft)
B
0.5 m (1.5 ft)
0.5 m (1.5 ft)
C
1.8 m (6 ft)
1.8 m (6 ft)
D
0.8 m (2.5 ft)
0.8 m (2.5 ft)
E *
2 m ( 7 ft)
2 m ( 7 ft)
The minimum clearances are based on nominal conditions of 22 °C (72 °F) at 30% RH, for the US 20
unit.
* Maximum equivalent straight length of flexible tubes.