Links XPS for Nortec GSTC/ SETC B+
|
23
Changing the IP Address (BACnet IP)
The IP address of the module can also be configured for BACnet IP networks. To configure the IP
address, a freely downloadable configuration program is required as mentioned in the previous
chapter.
To change the IP Address:
1.
Connect the computer to the ethernet port of the Links XPS module.
2.
Power up the module. During the boot process 8 multi-colored LED’s will illuminate and
remain steady. The module is ready when most of these LED’s have turned off.
3.
On the computer navigate to
Start > Programs > Fieldserver Utilities > Remote User
Interface
.
4.
A blue window will launch, any Links XPS models detected will be listed as “Fieldservers
discovered on the network”. If no modules are detected you will receive the following
screen:
Figure 20: No Links XPS Modules Detected
This error is most likely due to the network configuration of the computer. By default, the Links
XPS modules ship with an address of 192.168.10.11. If your computer is not already on the
192.168.10.0 domain, you will need to set your computer IP address to a unique address within
this range. You may need to turn off or disable any wireless connections before beginning to
avoid conflicts. For Windows systems, this setting is located in:
Содержание Nortec GSTC
Страница 3: ......
Страница 5: ......
Страница 50: ...Links XPS for Nortec GSTC SETC B 45 Figure 30 LonWorks Module LED...
Страница 54: ...Links XPS for Nortec GSTC SETC B 49 Figure 32 XPS Module BACnet Johnson N2 Figure 33 XPS Module LonWorks...
Страница 55: ...50 Links XPS Nortec GSTC SETC B...
Страница 56: ...Links XPS for Nortec GSTC SETC B 51...
Страница 57: ...52 Links XPS Nortec GSTC SETC B...
Страница 59: ......