TW-1 and TW-2 Thermolators use type “K” thermocouples to
sense the temperature in the return and supply process lines.
These thermocouples should be calibrated annually, or when a
new thermocouple is installed, to ensure correct operation.
The Thermolator’s Calibration Mode provides zero and span
calibration of both the supply and return line thermocouples.
You access the Calibration Mode while in Test Mode.
Press any button to display the first test menu.
Select the Calibration Mode menu.
Press and hold the Setpoint key for 3 seconds to index
to each test menu until the controller indicates “SC.L” in
the Actual display.
Release the Setpoint key.
You are now in calibration mode. Each press and release
of this key will exit the current calibration and start the
next calibration. The table below lists the calibrations that
will be performed.
Using the thermocouple calibrator, apply the
appropriate temperature to the control input.
C
ALIBRATING
T
EMPERATURE
S
ENSORS
Thermolator TW-1 and TW-2
UGH015/0100
5-10
M
AINTENANCE
Special Tools Needed:
❒
type K thermocouple
calibrator
2
3
4
5
SETPOINT
ACTUAL
CALIBRATION
DISPLAY
DISPLAY
Zero Calibrate Supply Sensor
32° F (0° C)
SC.L
Zero Calibrate Return Sensor
32° F (0° C)
rC.L
Span Calibrate Supply Sensor
510° F (266° C)
SC.H
Span Calibrate Return Sensor
510° F (266° C)
rC.H
Continued on next page
Содержание Thermolater vacuTrac
Страница 9: ...Figure 1...
Страница 12: ......
Страница 15: ......
Страница 16: ......
Страница 50: ......
Страница 62: ......
Страница 100: ......
Страница 106: ......
Страница 117: ...UGH015 0100 TW 1 230 460V WIRING DIAGRAM PD 5...
Страница 119: ...UGH015 0100 TW 2 230 460V WIRING DIAGRAM PD 7 2...