Page: 14
VL Series Portable Chillers, 0.25 to 1.5 Tons
UGH020/0301
3.1
GENERAL
A.
Failure to follow the factory required operation procedures may
adversely affect the unit’s ability to control process temperature and
may create a hazardous operating condition which may result in
unit damage and serious operator injury or death.
B.
The Operations segment of this manual is outlined below:
3.2
Machine start-up/operations procedure
- follow this
segment to start the unit after the initial installation or to
restart the unit after reinstallation to the same or different
process. This section includes information on system fill,
electric motor phasing (pump rotation) and process flow
adjustments.
3.3
Instrument
- follow this segment to start up and operate
the instrument controller. This section includes information
on automatic and manual venting, setpoint selection and
adjustment, and feature explanations.
3.4
Shut down procedure
- follow this segment to shut down
the unit. This segment includes information on system cool
down, shut down, electrical power supply precautions, and
disconnection from system.
3.2
START UP/OPERATIONS PROCEDURE
A.
SYSTEM FILL
1.
The unit has an internal reservoir which must be filled and
maintained for proper operation.
2.
Conair
recommends the addition of 20% inhibited
propylene glycol to the process fluid. This should help
prevent the process fluid from freezing and internal
components from rusting. A biocide must be added to the
water to prevent organism growth in the chilled water
system. See water treatment section in
section 8
of this
manual for more information.
3.
Remove the top panel
to access the reservoir.
Add fluid directly to the
reservoir tank. Please
note, when the pump is
first started, and after
the process lines are
filled and entrained air
is purged, additional
fluid may be required to
restore the reservoir to
the correct level.
Reservoir
Содержание 0.25 to 1.5 ton
Страница 4: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 4 THIS PAGE INTENTIONALLY BLANK...
Страница 8: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 8 THIS PAGE INTENTIONALLY BLANK...
Страница 22: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 22 THIS PAGE INTENTIONALLY BLANK...
Страница 26: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 26 THIS PAGE INTENTIONALLY BLANK...
Страница 32: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 32 THIS PAGE INTENTIONALLY BLANK...
Страница 41: ...Page 41 UGH020 0301 VL Series Portable Chillers 0 25 to 1 5 Tons 8 7 USEFUL ENGINEERING FORMULAS...