Page: 11
UGH020/0301
VL Series Portable Chillers, 0.25 to 1.5 Tons
2.3
DRAIN CONNECTION:
A.
The unit is supplied as standard with a ProCon type pump. In some
cases, it may be necessary to drain the unit. This is done by
removing the pump volute plug in the pump assembly.
B.
Note that if chemical treatment of process fluid or additives are use,
drainage shall be done according to local codes.
C.
It is important to note that drainage procedures must be done prior
to shipment or outdoor storage or the unit. If not, freezing damage
can occur.
2.4
AIR COOLED CONDENSER
A.
Air-cooled condenser require ambient air temperatures between
60°F and 95°F for efficient operation. Operating above 95°F may
result in elevated condensing pressures and eventual shut-down on
the high pressure safety switch. Check with the
Conair
service
department for more information on operating with ambient air
temperatures above 95°F or below 60°F.
B.
Air flow is generated by the motor driven fan. Air flow is from the
outside of the chiller, through the condenser and exhausted
through the unit. Exhaust air can not be ducted on motor driven
fan models.
C.
A free air space of at least four (4) feet is required at the condenser
intake and four (4) feet at the condenser discharge to allow for
proper air flow.
D.
At full load, this chiller will discharge approximately 15,000 BTU/hr
per hour per ton of cooling.
Thermocouple
Motor
Pump
Drain plug
Содержание 0.25 to 1.5 ton
Страница 4: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 4 THIS PAGE INTENTIONALLY BLANK...
Страница 8: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 8 THIS PAGE INTENTIONALLY BLANK...
Страница 22: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 22 THIS PAGE INTENTIONALLY BLANK...
Страница 26: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 26 THIS PAGE INTENTIONALLY BLANK...
Страница 32: ...VL Series Portable Chillers 0 25 to 1 5 Tons UGH020 0301 Page 32 THIS PAGE INTENTIONALLY BLANK...
Страница 41: ...Page 41 UGH020 0301 VL Series Portable Chillers 0 25 to 1 5 Tons 8 7 USEFUL ENGINEERING FORMULAS...