background image

Sentinel 150P installation, operation & maintenance 

ci0050   p5/8   issue 5   2014-08-26 

 

TC: Temperature Compensation 

CN1 

pin 

Function 


RTC (remote temperature compensation)  
Ground (for RTC sensor return) 

These terminals allow optional connection of a Computronic 
RTC temperature sensor. With the RTC sensor connected, 
and the sensor head positioned to give the most accurate/ 
representative measurement of battery temperature, the 
SNTL150P will automatically vary DC output voltage for 
optimal charging. 

Temperature compensation is enabled automatically 
when a remote RTC sensor is connected. For each 1°C 
change in ambient temperature above or below 20°C 
(within the range -10 to +50°C), output voltage 
automatically varies by 3mV per cell. Increasing ambient 
temperatures causes decreasing output voltages; 
decreasing ambient temperatures causes increasing 
output voltages.  

CN1 terminals 3 and 4 are designed for connection to a 
Computronic RTC sensor only. DO NOT connect other 
types of temperature sensor, such as thermocouples, 
thermistors or resistance probes. The standard 
Computronic RTC sensor (part code 42.70.3619) includes 
a 3 metre lead assembly. Non-standard lead lengths are 
available to special order. 

An RTC sensor short-circuit fault is indicated by a fast-
flashing red LED in the Sentinel's protective cover. 

If no RTC sensor is connected, temperature 
compensation is automatically disabled and the output 
voltage does not vary with ambient temperature.

 

Programmable input and output 

CN1 

pin 

Function 



Relay output (swve DC) 
Output/input common return (

–ve DC) 

Input (

–ve DC to activate) 

Model codes with suffix 'A' (models SNTL150P...CDA) 
additionally include one relay output and one digital 
(switch) input. The functions of input and output can be 
configured using the SNTL150P-PCSUITE software tool. 

Output 

The swDC relay output allows the signalling of 
battery and charger faults to remote alarms, annunciators 
or other equipment. Maximum output load is 1A @ 
30VDC. 

The software tool allows configuration of the output to 
activate on one or more fault conditions: 

  mains fail * 

  DC connection error * 

  battery missing 

  remote temp sensor short 

  high voltage alarm 

  low voltage alarm 

  charge fail alarm * 

* enabled as factory default 

For most combinations of the above faults, the output 
relay operates as follows: 

Charger conditions 

Pin 5 relay output state 

Normal operation, no faults  + DC 

(relay energised) 

Any fault 

Open circuit  
(relay de-energised) 

The exception to the rule above is when the output is 
configured to signal ONLY high battery voltage, in which 
case relay operation is: 

Charger conditions 

Pin 5 relay output state 

Normal operation, no faults  Open circuit  

(relay de-energised) 

High battery voltage fault 

+ DC 
(relay energised) 

See software tool document ci0052 for full information on 
programmable alarm output options.

 

Input 

– optional charger control 

Input pin 7 is activated by connection to battery negative 
DC (e.g. connection to pin 6 via external relay/switch 
contacts).  

The input can be used for optional control of several 
charger functions, depending on the application and 
levels of control needed. Programmable input functions 
include: 

  return to float mode 

  ramp to boost  

  boost extension 

 perform battery check 

 reduce to nominal voltage 

 turn output off 

For full details of all programmable input functions, please 
refer to SNTL150P-PCSUITE installation manual, 
document reference ci0052. 

Electrical Connection & Configuration (cont.) 

 

Содержание Sentinel 150P series

Страница 1: ...change our specifications and designs at any time Computronic Controls products and the Computronic Controls logo are registered and or common law trademarks of Enovation Controls LLC This document i...

Страница 2: ...and damage to property ix DANGER OF EXPLOSION NEVER CHARGE A FROZEN BATTERY PRIOR TO INSTALLATION COMMISSIONING Clean battery terminals Be careful to keep corrosion from coming into contact with eyes...

Страница 3: ...cover for surface mounting in an enclosed panel Electrical connection of the AC supply battery and control circuits is via screw terminal blocks Model options Model codes with suffix A SNTL150P CDA ad...

Страница 4: ...y block for connection of the DC charge output temperature compensation remote sensor relay output and configurable input Use a 5 mm 0 2 in flat head screwdriver to tighten loosen the terminals For th...

Страница 5: ...uffix A models SNTL150P CDA additionally include one relay output and one digital switch input The functions of input and output can be configured using the SNTL150P PCSUITE software tool Output The s...

Страница 6: ...AWG or larger wire conductors rated for temperature 90 C 194 F The AC live wiring must incorporate fuse ratings types as indicated on the charger labelling Sentinel PC connection SNTL150P PCCON confi...

Страница 7: ...ease in output voltage It may be initiated automatically on battery low voltage programmable level factory default 12 0V 24 0V automatically on expiry of a time interval since the last AutoBoost progr...

Страница 8: ...Sentinel 150P installation operation maintenance ci0050 p8 8 issue 5 2014 08 26 Fault Finding Warranty and Maintenance Troubleshooting Flowchart...

Отзывы: