Rev.01 03-27-17
Page 44 of 67
Compu-Aire
10.3
BACNET OVER TCP/IP
10.3.1
Installation
The board is installed in the CONTROLLER controller, when off, as follows
1.
Remove the “Serial Card” cover from the
controller using a screwdriver.
2.
Insert the board in the corresponding plug-in connector, making sure it is fully inserted
and in contact with the two supports located on the case of the CONTROLLER. This
operation may be difficult due to the limited space, consequently, it is recommended to
insert the board at an angle and then turn it until aligning the connectors.
3.
Close the cover again, using the cover supplied with the board, lining up the connector
on the serial board with the opening in the cover.
4.
(optional): stick one or both labels supplied outside and/or inside the electrical panel
near the controller, so that the MAC ADDRESS can be read without needing to open the
electrical panel for the connection to the Ethernet network, use an S/FTP cable,
category 5e or higher.
10.3.2
Functions
The pCOWeb board is used to connect the controller to an Ethernet network and consequently
perform the following functions.
•
Access the information on the controller (network variables and parameters) using an
Internet browser, such as Internet Explorer™ instal
led on a PC and connected to the
pCOWeb via TCP/IP (see Web server)
•
Connection to a supervisory network that uses one of the following standard protocols
o
SNMP v1 & v2c
o
BACnet Ethernet ISO8802-2/8802-3
o
BACnet/IP
10.3.3
Default parameters
In order to access the configuration (see the Configuration section), the pCOWeb can be started
using the “factory bootswitch parameters”:
•
IP address= 172.16.0.1 Net mask= 255.255.0.0;
•
“root” user password: froot
•
“httpadmin” user password: fhttpadmin
•
“guest” user password: fguest