CONDENSATE DRAIN
Evaporator and the condensing sections (air cooled only) are provided with individual condensate drains, 3/4"
stub. Hook both drains with "P" traps. Provide 1/4" slope per 10 feet.
CAUTION:
Drain line contains boiling water from humidifier. Use copper or other
Suitable material for the drain.
NOTE: COMPU-AIRE HIGHLY RECOMMENDES AN AUXILIARY DRAIN PAN TO BE
PROVIDED UNDER THE UNIT. (TO BE FIELD FURNISHED AND INSTALLED BY OTHERS)
AIR FLOW
The evaporator and the condensing sections are provided with variable pitch motor pulley which are field
adjustable. Refer to the specification data for the air flow data. In case field adjustments are made, check to
verify the motor full load amps.