Compool Lx220
Water Sensor
Select a convenient location to mount the Water Sensor in the plumbing system between the
filter pump and filter. Drill a 5/16” dia. hole in one side of pipe, and install one of the
Temperature Sensors (included) in accordance with instructions provided. Run 22 gauge 2-
conductor cable (included) between the Sensor and low voltage compartment of the Solar
Control. Use waterproof connectors (provided) to connect Sensor to cable. At the Solar Control,
strip insulation 1/4” and connect to the circuit board at WATER SENSOR screw terminals.
Solar Sensor
Install the other Temperature Sensor at the solar panel array, or any sunny location.
WARNING: DO NOT DRILL HOLE AND CLAMP SENSOR INTO SOLAR PIPE. For
glazed panels, install Sensor between collector and glazing. Run 2-conductor cable between the
Sensor and the Solar Control. Use waterproof connectors (provided) to connect Sensor to cable.
At the Solar Control, strip insulation 1/4” and connect cable to the circuit board at SOLAR
SENSOR screw terminals.
High Voltage Wiring
The high voltage wiring section is located behind the service panel in the lower right side
compartment of the Solar Control. Holes are provided on bottom of enclosure for conduit
mounting. The Solar Control can be connected either to 115VAC or 230VAC. The Solar
Control should be wired so that it gets continuous power (connect to Line-Side of Time Clock
or directly to sub-panel).