VAX 7000 Model 810
VAX Systems 4.39
Specifications
Physical Characteristics Operating
Shipping
Height
Width
Depth
Weight, full configuration
Without batteries
With batteries
170.0 cm (67.0 in.)
80.0 cm (31.5 in.)
87.5 cm (34.4 in.)
408 kg (900 lb)
545 kg (1200 lb)
195.0 cm (76.7 in.)
109.5 cm (43.1 in.)
121.0 cm (47.5 in.)
448 kg (1000 lb)
585 kg (1300 lb)
Clearances
Operating
Service
Front
Rear
1.0 m (40 in.)
1.0 m (40 in.)
1.5 m (59 in.)
1.0 m (40 in.)
Environmental
Operating
Nonoperating
Temperature
Humidity
Altitude
Vibration
Heat dissipation
1
15° to 28° C (59° to 82°F)
20% to 80%
0–2.4 km (0–8000 ft)
2–22 Hz @ 0.01"da minimum
Fully Configured System
(System Cabinet)
17,700 Btu/hr, 5,200 W
Minimally Configured System
2
(System Cabinet)
3,400 Btu/hr, 1,000 W
-40° to 66° C (-40° to 151°F)
10% to 95%
9,100 m (30,000 ft)
22–500 Hz @ 0.25g maximum
Fully Configured System
(System Cabinet with Two
I/O Expansion Cabinets)
47,000 Btu/hr, 13,800 W
Power requirements
3
U.S./Canada
Europe/APA
Japan
Nominal voltage
Frequency range
Phases
Maximum input
current/phase
Surge current
Rating
Power cap (system)
Receptacle (site)
Receptacle
PCS/PDS/PDU/UPS cable
120/208 V
50–60 Hz
3-phase star
4-wire N-GND
24 A rms
50 A peak
30 A
DEC 12-12314-00
DEC 12-12315-01
NEMA L21-30R
BC24W
380–415 V
50–60 Hz
3-phase star
4-wire N-GND
12.8 A rms
50 A peak
16 A
DEC 12-30333-02
See footnote 4
IEC309
BN29X
202 V
50–60 Hz
3-phase delta
4-wire mid-GND or
3-wire junction-GND
24 A rms
50 A peak
30 A
DEC 12-12314-00
DEC 12-12315-01
NEMA L21-30R
BC24W
1.Power system provides unity power factor which allows full use of input line current
(watts=VA). Approximate Btu's for a given system configuration can be calculated by
multiplying the “EPU” value per cabinet by 85.4.
2.Minimally configured system contains one regulator, one CPU module, one memory
module, one IOP module, and one Ethernet controller.
3.Power cord is required for system cabinet and each I/O expansion cabinet.
4.Receptacle type is Hubbell 516R6 or equivalent.