QuickSpecs
ProLiant
BL20p and p-Class system
DA-11411 World Wide — Version
4
— September 19, 2002
22
Technical Specifications
Single-Phase Model
Three-Phase Model
Dimensions
Height
5.25 in/13.34 cm
5.25 in/13.34 cm
Width
27.15 in/68.96 cm
27.15 in/68.96 cm
Operating and Performance
Specifications for Power
Enclosures
(North America/Japan)
Depth
17.60 in/44.7 cm
17.60 in/44.7 cm
Weights
No hot-plug power supplies
47.5 lb/21.55 kg
47.5 lb/21.55 kg
All hot-plug power supplies
99.5 lb/45.13 kg
125.5 lb/56.93 kg
Input requirements
Rated input voltage
200 VAC to 240 VAC
200 VAC to 240 VAC line
to line
Rated input frequency
50 Hz to 60 Hz
50 Hz to 60 Hz
Rated input current per side
24A
24A per phase
Rated input power per side
5760 W
9976 W
Power cord
1 NEMA L6-30P per side 1 NEMA L15-30 per side
Rated output voltage
-48.8 VDC to -54 VDC
-48.8 VDC to -54 VDC
Output voltage
specifications
Rated output current
99A 170A
Rated output power
4298 W
8310 W
Nominal power
4158 W at 208 VAC
7202 W at 208 VAC
Operating
50° to 95° F/10° to 35° C 50° to 95° F/10° to 35° C
Ambient temperature
range
(See note)
Shipping
-22° to 140°F/-30° to 60°C -22° to 140°F/-30° to 60°C
Operating
20% to 80%
20% to 80%
Relative humidity,
non-condensing
(See note)
Non-operating
5% to 95%
5% to 95%
Operating
82.4° F/28° C
82.4° F/28° C
Wet bulb temperature
Non-operating
101.7° F/38.7° C
101.7° F/38.7° C
Note: Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No direct sunlight. Upper
operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft/ 9,144 m or
30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa.