CompAir DELCOS Pro Скачать руководство пользователя страница 15

5. Extended functions 

13 

If there are no days of the week selected in the 
switching unit line, the switching unit is not active. The 
switching unit only becomes active when the day of the 
week is set. When the 

 

is pressed, the first 

underscore _ starts to flash. You can now use the 

  

 

key to set the first day of the week (Sunday). Then use 
the 

 

key to confirm the day of the week. The next 

underscore _ then starts to flash. If you do not want to 
confirm a day of the week as set, please immediately 
press 

You can run through all seven days of the 

week in this way. Once you have confirmed the last day 
of the week (Saturday), the first unit of the switch-in -
point starts to flash. You can either set this using 

  

or

 

 

 . Once the last unit of the switch-out point has been 

confirmed, the whole timer unit is activated. 

The next step is to go to the 

[

 

CONTROL

 

MENU

 

]

 sub-

menu and then the 

TIMER

 

CONTROL

 menu item. You 

will now see the default setting 

TIMER

 

CONTROL

 

OFF

If you press the   key, the 

OFF 

value starts to flash. 

You can now use the 

  

key to change the value to 

ON 

. Then please press the   key again to confirm the 
entry. The timer is now switched on. 

 

To improve your understanding of this function, the 
timer unit setting is explained below using various 
examples. 

 

Example 1: 

Switching unit 1 not active: 

1 _______ 00:00 00:00 

 

Example 2: 

The unit should run Monday to Friday between 7.30 am 
and 4.15 pm. 

2 _MTWTF_ 07:30 16:15 

  

 

a) 

b) 

c) 

 

a)  Days of the week Monday to Friday 
b)  Switch-in point 
c)  Switch-off point 

 

 

Example 3: 

The unit is to run from Sunday 10 pm through 
continuously to Saturday 2 pm. However during the 
daily break (12 midday to 12.30 pm), the unit is to be 
shut down. 

You will now have to use various switching units. The 
following settings would be needed in this case: 

1 S______ 22:00 00:00 

a)

 

2 _MTWTFS 00:00 12:00 

b)

 

3 _MTWTF_ 12:30 00:00 

c)

 

4 ______S 12:30 14:00 

d)

 

5 _______ 00:00 00:00 

6 _______ 00:00 00:00 

7 _______ 00:00 00:00 

a)  Start of operating period 
b)  Operating period up until lunch break 
c)  Start of operation after lunch break 
d)  End of operating period 

 

5.3.2  Pressure changeover setting 

Please go to the 

[

 

TIMER

 

CONTROL

 

]

 sub-menu. There 

you can use 

  

or

 

 

 

 

 to select between  various timer 

units. The timer units of the 2nd (

p

2

) pressure range are 

in the menu under the normal timer units. 

 

 

CUT-OUT POINT

 

CUT-IN POINT  

 

p2 CUT-OUT

 

p2 CUT-IN 

 

 

 

 

p2 TIMER CONTROL 

 

 

 

 

 

 

 

 

 

ON-LOAD 

Fig. 2  Pressure changeover block diagram 

 

Содержание DELCOS Pro

Страница 1: ...GB Id no 100013596 03 January 2010 1 Original User Manual DELCOS Pro electronics for stationary rotary screw compressor...

Страница 2: ......

Страница 3: ...1 German basis BA 100013595 03 Valid as of software version DPro L 1 xx We reserve the right to modifications relating to technical advances...

Страница 4: ...rogramming maintenance intervals 9 4 3 Total load hours counter 9 5 Extended functions 10 5 1 CONTROL MENU sub menu 10 5 1 1 Operating modes 10 5 1 2 Second pressure range p2 10 5 1 3 Dryer pre run 10...

Страница 5: ...al compression pressure is the pressure measured downstream of the compressor stage Network pressure is the pressure within the system connected downstream of the compressor The following symbols may...

Страница 6: ...START IN xxs alternating with AFTER POWER LOSS A power loss has caused the unit to shut down The automatic restart function has been selected in the control menu The unit now starts automatically aft...

Страница 7: ...0 00 00 p27 __________ 00 00 00 00 01 EM STOP 12345h 01 EM STOP 12300h CUT OUT POINT 13 0bar CUT IN POINT 12 5bar p2 CUT OUT POINT 10 5bar p2 CUT IN POINT 10 0bar AUTOMATIC OPERATION ENABLE REMOTE STA...

Страница 8: ...CONTROL MENU FAULT MEMORY TIMER CONTROL LIMIT VALUES OPTIONAL IN OUTPUTS Enter a sub menu by pressing the key Again here you can use the or keys to go to a menu item To exit the sub menu you must pre...

Страница 9: ...e set by pressing the key Note The control system checks whether the value set can be used The maximum network pressure CUT OUT POINT must be at least 0 2 more than the minimum network pressure CUT IN...

Страница 10: ...requirement from the compressed air system and the unit is in CONTINUOUS OPERATION it switches to OFF LOAD This means that the motor and compressor stage run but no air is pumped into the compressed...

Страница 11: ...maintenance interval should be reprogrammed The maintenance message can be acknowledged using the key 4 2 Programming maintenance intervals To program a maintenance interval please go to the MAINTENAN...

Страница 12: ...second pressure range function in the CONTROL MENU sub menu The relevant menu items there are p2CUT OUT POINT 10 5bar p2CUT IN POINT 10 0bar p2TIMER CONTROL OFF You can use p2CUT OUT POINT and p2CUT I...

Страница 13: ...it features several compressors This in turn ensures that the power supply is not loaded unnecessarily 5 1 6 Unlimited autom re start after power loss The control system can perform an automatic re st...

Страница 14: ...sion pressure and network pressure When accessed these values flash to clearly show that they are not the current display values To access this information please use or to go to the warning message o...

Страница 15: ...entry The timer is now switched on To improve your understanding of this function the timer unit setting is explained below using various examples Example 1 Switching unit 1 not active 1 _______ 00 0...

Страница 16: ...for the 2nd pressure range 5 4 Limit values sub menu The LIMIT VALUES sub menu is for information only Here you can access the parameters set in the factory The following are shown a DESIGN PRESS 13 0...

Страница 17: ...not assigned programmed EXT FAULT If the contact is opened the EXT FAULT fault message appears on the display and the unit is shut down shutting down is delayed by 1sec EXT WARNING If the contact is...

Страница 18: ...e no faults on the compressor WARNING The output relay is activated when there are no warnings on the compressor MAINT ELAPSED The output relay is activated when there are no maintenance messages on t...

Страница 19: ...ed twice for codes 2 and 3 If you have entered a code incorrectly the indication immediately jumps back to code 1 You then have to re enter all three codes If you have correctly entered the codes the...

Страница 20: ...AD Fig 5 Circuit diagram for pressure changeover Sections 5 1 2 and 5 3 2 contain explanations of how to set the second pressure range and the possibility of timer operations with the second pressure...

Страница 21: ...now be switched to on load or off load using these two inputs You will find a circuit diagram in Fig 6 In our explanation we have assigned the inputs as follows INPUT 1 ENAB REM LOAD INPUT 2 REMOTE L...

Страница 22: ...e key to change the value to ON The symbol appears in the first display row Please connect the potential free contact that you need for the remote start stop function to the X2 1 and X2 3 terminals Th...

Страница 23: ...must not exceed 55 C 4 All remote controls fitted at a later date remote On Off must be managed without a connection relay at max 20 metres from the control cabinet 5 When commissioning and carrying...

Страница 24: ...tive cooling Improve Unit being operated with enclosure open Close enclosure Oil injection volume temperature too low high Check find cause Incorrect oil grade viscosity Check replace oil if necessary...

Страница 25: ...PUT EXT WARNING 3 Check find cause FAULT BEKOMAT FAULT Connected condensate drain valve Bekomat defective 3 Check find cause WARNING BEKOMAT WARN Connected condensate drain valve Bekomat defective 3 C...

Страница 26: ...ef pressure requirements during the run on time No compressed air requirements within the switching points set 4 Pressure changeover by timer or external contact active 5 1 Unit specific setting see 5...

Страница 27: ......

Страница 28: ...Gardner Denver Deutschland GmbH Argenthaler Str 11 55469 Simmern Germany Tel 49 0 6761 832 0 www compair com e mail sales compair com...

Отзывы: