background image

INS_FVT/FVR8018SHR_REVA

11/14/11

PAGE 7

TEcH SUPPORT: 1.888.678.9427

INSTALLATION AND OPERATION MANUAL 

FVT/FVR8018SHR

FIGURE 9 – SHR SWITCH POSITIONS

FIGURE 10 – LED INDICATORS

OPTIc A/B

VIDEO

DATA

POWER

GREEN

Communication link has been established 
over optical fiber

An active video signal is present on 
the bNC connector.

An active data signal is present on the 
pins of the data connector.

Unit powered up

RED

Communication link has not been 
established. 

No video signal is present.

GREEN/RED 

BLINK

Communication has been established 
over optical fiber. However a fiber break 
has been detected in the system.

OFF

Unit powered down

Unit powered down

No data signal is present.

Unit powered down

Remote Fault Locator (RFL) using the OPTIc LEDs

The bi-color oPTIC A and oPTIC b lEds on the front panel convey the status of the optical link between one unit and the next unit around the ring, as well as 

the status of the ring as a whole. They can be used to identify the location of a remote fiber fault based on their color and pattern:

•  Solid Green    Optical link has been established between this optical port and the adjacent unit over fiber.

 

Furthermore, every other unit in the system is also reporting that link has been established.  

There are no faults in the system.

•  Solid Red  

 Optical link over this port has been lost.

 

This could be due to a broken fiber, a bad connection, or loss of power at the adjacent unit.

•  Blinking  

Green/Red  

 Optical link has been established between this optical port and the adjacent SHR unit. 

However, a fault condition has been detected somewhere in the system. The oPTIC lEd will be green for a period of time, and 

then flash red some number of times. The number of red flashes indicates the location of the fault by “hops” around the ring. If 

the lEd flashes red three times, then the location of the fault is three hops away (i.e. three SHR units away). For larger systems 

with faults greater than 9 hops away, the lEd will use a combination of long and short red flashes. Each long flash indicates 10 

hops. Each short flash indicates 1 hop.  For example, a fault 47 hops away would be encoded as 4 long red flashes, followed 

immediately by 7 short red flashes. The pattern repeats indefinitely until the fault is resolved.

SHR Switch 2

 can disable the Remote Fault locator (RFl) feature of the oPTIC 

A and oPTIC b lEds as described in Figure 10. For self-healing ring topologies, 

this switch would normally be turned oFF at every unit in the system so that 

the RFl is enabled. However, for linear topologies this switch would be turned 

oN at the two end points and turned oFF at the rest of the units. disabling the 

RFl at these two locations prevents them reporting their disconnected optic 

ports as a fault to the rest of the units in the system. Fiber breaks throughout 

the rest of the system will still be reported normally, even at the two end-

points. It is also possible to completely disable the RFl by setting this switch to 

the oN position at every unit in the system. In this case, the oPTIC A and oPTIC 

b lEds will only report the status of the optical link between this unit and the 

next; the lEds would either be solid green or solid red.

DcH1/SHR Switch

Resulting configuration

1

2

NA*

ON

disable Remote Fault locator (RFl) feature

NA*

OFF

Enable Remote Fault locator (RFl) feature

*  Switch 1 on the FVT/FVR8018SHR unit is not used currently and is reserved 

for a future release.

Содержание FVR1010SHR

Страница 1: ...r an electrical interface of RS232 RS422 or RS485 2 Wire or 4 Wire Utilizing wave division multiplexing WDM technology only one optical fiber is required between units It s possible to implement a ful...

Страница 2: ...al Connector for Rack Mount Units MULTIMODE OR SINGLE MODE OPTICAL FIBER Depending on Model BLACK BLACK WITH WHITE STRIPE Power Supply Surface Mount 8 15 VDC 3W Rack Mount From Rack FIGURE 2 FVT8018SH...

Страница 3: ...nchester DIN DIN DOUT DOUT Data Out Data Out Data In Data In 2 Wire RS485 DIN DIN DIN DIN Data A Data B Data A Data B Data Transmit Data Receive Signal Ground DIN DOUT GND DOUT DIN GND Data Receive Da...

Страница 4: ...INS_FVT FVR8018SHR_REVA 11 14 11 PAGE 4 Tech Support 1 888 678 9427 INSTALLATION AND OPERATION MANUAL FVT FVR8018SHR FIGURE 5 RJ45 BREAK OUT 5 pc Factory Supplied...

Страница 5: ...ed using a pair of switches on the front panel of the unit Switch FIGURE 7 SWITCH SETTINGS RS232 1 NC 2 Out A 3 Ground A 4 NC 5 OUT B 6 IN A 7 GROUND B 8 IN B RS485 2W SENSORNET 1 NC 2 NC 3 IN A 4 NC...

Страница 6: ...nits in the ComNet SHR Product Line Note that Optic A is always connected to Optic B on the next unit FVT4014SHR FVR1010SHR FVT4014SHR FVR4014SHR FVR8018SHR OPTIC A OPTIC B OPTIC A OPTIC B OPTIC A OPT...

Страница 7: ...will be green for a period of time and then flash red some number of times The number of red flashes indicates the location of the fault by hops around the ring If the LED flashes red three times the...

Страница 8: ...n is connected to an audible alarm to indicate faults Three receivers are used in this example but there is no limit to the number of receivers used in a system This example could also be expanded to...

Страница 9: ...reserved for a future release A B The figure below shows a system of four FVT1010SHR units a FVT4014SHR unit and a FVR8018SHR unit connected as a self healing ring Eight channels of video enter the sy...

Страница 10: ...mes 6 Green then blink Red 2 times Green then blink Red 3 times FVT1010SHR Unit 1 FVT1010SHR Unit 3 FVR8018SHR Unit 6 FVT1010SHR Unit 2 FVT4014SHR Unit 5 FVT1010SHR Unit 4 V V VIDEO OUT 1 8 e g Bank o...

Страница 11: ...oriented right side up and slide it into the card guides in the rack until the edge connector at the back of the card seats in the corresponding slot in the rack s connector panel Seating may require...

Отзывы: