4. Commissioning
MF0150A1A.doc
Manual for ION-M17EHP/19P
Page 35
Alarm Outputs
(Pins 6 and 7 are not connected)
figure 4-12 Alarm outputs (optocoupler)
figure 4-13 Flange connector, 7 poles
The alarm outputs (pins 1 to 4: open collector output 5 V / 1 mA; see
figure 4-13
) are
normally low. In case of an alarm they are high active (5 V). They can be used to
monitor alarms with an external alarm indicator.
Note:
The manufacturer / supplier of this system assumes no liability for
damage caused by equipment connected to external outputs or by
effects from such equipment.