Figure 14. Routing Patch Cord through Tray Assembly
5. Route the pigtail into the cable management tray through the opening near the tray hinge
as shown in
6. From the entry point, route the pigtail to the tray outer channel and then wrap it in a circular
direction. Make certain that the pigtail lies flat and does not protrude from the tray.
7. Continue wrapping the pigtail through the tray channels working your way to the center
circle until all excess pigtail length is stored.
8. As the slack is used up allow enough to route the pigtail out of the tray to the original entry
point.
9. Route the pigtail out of tray through the opening near the tray hinge.
10. Apply numbered identification labels (provided) to each pigtail and mark cable
designations on front of cable management trays.
11. Repeat procedure for each patch cord to be stored. Close front cover when complete.
Caution:
Do not kink or make a sharp bend in the patch cord when forming loop. Excessive
bending may damage the optical fiber within the patch cord
.
15371-A