ADCP-90-459 • Issue 2 • June 2016
Page 21
© 2016
CommScope
. All Rights Reserved.
6. To connect an individual cable connector to a micro-VAM, lift up the release tab on top of
the micro-VAM and slide the micro-VAM upward (see
Figure 26
on page 28). Pull the
micro-VAM dust cap straight out and connect the connector to the micro-VAM port.
7. Secure the cables on the side and rear of the tray as shown in
Figure 16
on page 19.
Figure 18. Cable Routing for 72-Position Micro-VAM Tray
Left or Right Entry (Use Either This or Mirror Image)
6.2.4
48-Position Termination/Splice
Cables routed into the tray for splicing or termination are normally multifiber cable assemblies.
Cables to be spliced will be bare-ended. Cables to be terminated will be pre-terminated. The
2RU FMT will also have factory-installed, internal pigtails between splice tray and connector
bulkhead. Refer to the following instructions.
Note: Always clean and inspect connectors and adapters before mating them. For
guidelines, refer to ADCP-90-159.
18649-B
LEFT OR RIGHT