background image

To the Installer

R

Thank you for choosing 

CommBox Room 

Movement Sensor (RMS)

 

The RMS uses passive infra-red technology 

to detect movement in a room. It is 
intended to be used with the CommBox 

range of control systems to automatically 
shut down equipment in the room after a 

period of time when no movement is 
detected, so saving energy and 

maximising projector lamp life. 
Before commencing installation, please 

read these instructions carefully to get the 
best results from your RMS.

For your safety

Please ensure that any wiring used to 
connect RMS to other equipment is kept 

clear of mains wiring and follows 
applicable local wiring codes. Under 

no 

circumstances

 may an RMS be connected 

directly to power mains wiring.
Make sure that the power supply you are 
using meets your local safety regulations 

and that its voltage does not exceed 15 
volts DC. Unregulated power supplies can 

output voltages that are well above what is 
shown on their label.
The RMS is intended for 

indoor

 use only.

Mounting

Choose a location on a wall that is 

preferably 3 to 4 metres from the floor, not 
adjacent to heating or air conditioning 

outlets or opposite windows and where 
people moving in the room can be “seen” 

by the RMS.
Remove the cover by placing a small flat-

bladed screwdriver in the bottom of the 
case and gently prise the cover off.

DO NOT TOUCH THE PYRO SENSOR 
INSIDE WITH YOUR FINGERS!

You may remove the circuit board to 
facilitate mounting the base to the wall. To 

do this, lift the white plastic tab at the 
lower side and push the board up until it 

clears the keyhole slot at the top. At this 
point the board may be lifted out of the 

base.
When replacing the board, to achieve 

optimum coverage, adjust the position of 
the board in the base to match the height 

of the RMS above the floor. Moving the 
board higher will lower the beam angle. 

Please refer to the Mounting Height scale 
on the right-hand side of the board.
After wiring, refit the cover with its lens. 
The cover must be in place in order to test 

the RMS.

This product 
conforms to the 

EMC directive 
89/336 CCE

Keyhole 
slot

Cable 
access 

knockout

Mounting 
height 

pointer

Mounting 

hole 
knockout

Pyro 

sensor

White plastic 

tab