CSCMA-APH-6-SM1907A
R410A All DC Inverter Mini VRF
Specifications & Performance 51
8. Electric Characteristics
Model
Outdoor Unit
Power Supply
Compressor
OFM
Hz
Voltage
Min. Max. MCA TOCA MFA MSC
RLA
kW
FLA
CSCMA-APH004-6SB
60
208-230
187
253
27.5
24
32
/
9.7
0.17
1.7
CSCMA-APH005-6SB
60
208-230
187
253 31.25
30
40
/
13.5
2×0.1
2×0.9
CSCMA-APH006-6SB
60
208-230
187
253 36.25
30
40
/
13.5
2×0.1
2×0.9
CSCMA-APH007-6SB
60
208-230
187
253 36.25
30
40
/
16.1
2×0.1
2×0.9
Remark:
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
RLA: Rated Locked Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
kW: Rated Motor Output (KW)
9. Sound Levels
Model
Noise level dB(A)
CSCMA-APH004-6SB
57
CSCMA-APH005-6SB
57
CSCMA-APH006-6SB
57
CSCMA-APH007-6SB
57