R410A All DC Inverter Mini VRF CSCMA-APH-6-SM1907A
12 Specifications & Performance
Model
CSCMA-APH006-6SB
CSCMA-APH007-6SB
Code
220095101890
220095102980
Outdoor fan motor
Capacitor
uF
/
/
Speed
r/min
800
800
Outdoor fan
Material
ASG20
ASG20
Type
Axial fan
Axial fan
Diameter
in.(mm)
20(508)
20(508)
Height
in.(mm)
6-11/16(170)
6-11/16(170)
Outdoor coil
Number of rows
2
2
Tube pitch(a)x row
pitch(b)
in.(mm)
7/8 x3/4 (22 x 19.05)
7/8 x3/4 (22 x 19.05)
Fin spacing in.(mm)
1/16(1.6)
1/16(1.6)
Fin type (code)
Hydrophilic aluminum
Hydrophilic aluminum
Tube outside dia.and
type
in.(mm)
5/16(
Ф7.94
)
5/16(
Ф7.94
)
Inner groove tube
Inner groove tube
Coil length x height
in.(mm)
50-1/4 x 34-1/4(1276 x 870)
50-1/4 x 34-1/4(1276 x 870)
Number of circuits
7
7
Outdoor air flow
CFM(m
3
/h)
3531(6000)
3531(6000)
Outdoor sound level(sound pressure level )
dB(A)
57
57
Outdoor unit
Dimension
(W x H x D)
in.(mm)
35-7/14x52-1/4x 15-3/4(900x1327x400)
Packing
(W x H x D)
in.(mm)
40-35/64 x 57-21/64 x 17-1/8(1030 x1456 x435)
Net/Gross weight
Lbs(kg)
209.4/233.7 (95/106)
224.9/249.1(102/113)
Refrigerant
Type
R410A
R410A
Charged volume
Lbs(kg)
8.6 (3.9)
8.6 (3.9)
Throttle type
Electronic expansion valve
Design pressure
MPa
4.4/2.6
Refrigerant piping
Liquid side
in.(mm)
Ф
3/8(
Ф9.5
3)
Ф
3/8(
Ф9.5
3)
Gas side
in.(mm)
Ф
5/8(
Ф
15.9)
Ф
3/4(
Ф
19.1)
Total Pipe
Length(Actual)
ft.(m)
328(100)
328(100)
Max. difference in
level
ft.(m)
26(8)
26(8)
Connection wiring
Power wiring
mm
2
3 core x 4.0
3 core x 4.0
Signal wiring
mm
2
3 core shielded wire x 0.75
3 core shielded wire x 0.75
Ambient
temperature
℉
(
℃
)
Cooling 5~109.4
℉
(-15
~
43
℃
) Heating 5~80.6
℉
(-15
~
27
℃
)
Notes:
1. The cooling conditions: indoor temp.: 27
℃
DB (80.6
℉
), 19
℃
WB (66.2
℉
) outdoor temp.: 35
℃
DB (95
℉
) equivalent pipe length:
5m drop length: 0m.
2. The heating conditions: indoor temp.: 20
℃
DB (68
℉
), 15
℃
WB (44.6
℉
) outdoor temp.: 7
℃
DB (42.8
℉
) equivalent pipe length:
5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 3.28ft (1.0m) in front of the unit at a height of *m (1m
(3.28ft.)for 105 model,1.2m(3.94ft.) for 120~160 model ). During actual operation, these values are normally somewhat higher as
a result of ambient conditions.
4. The above data may be changed without notice for future improvement on quality and performance.
Содержание VRFPLUS CSCMA Series
Страница 1: ...VRF CSCMA SERIES 220V 1Ph 60hz ETL SERVICE MANUAL ...
Страница 3: ...R410AAll DC Inverter Mini VRF CSCMA APH 6 SM1907A ...
Страница 19: ...R410AAll DC Inverter Mini VRF CSCMA APH 6 SM1907A 16 Specifications Performance 5 Wiring Diagrams For 10 5kW ...
Страница 20: ...CSCMA APH 6 SM1907A R410AAll DC Inverter Mini VRF Specifications Performance 17 For 12 14 16kW ...