22
2.3.
Connection
2.4.
Power supply
Before connecting the unit, verify that the supply voltage matches the operating voltage of the heat pump.
The RCD plug has been included with power cable, which can offer electrical protection against an electrical
shock caused by a possible short circuit inside the unit.
Attention!
The RCD plug is not waterproof and must be protected against any damage and used in a dry
environment.
Cable selection of the RCD plug:
* Above data may be subject to modification, without prior notice.
Note: the above date is adapted to a power cord
≤ 10 m. Is the power cord is over 10 m, the wire diameter must
beincreased. The signal cable can be extended to 50 m at most.
Model
EasyHeat 3
EasyHeat 5 EasyHeat 6
Breaker
Residual-current circuit breaker
4.5
8.0
9.0
Rated residual leakage current
30
30
30
Fuse
4.5
8.0
9.0
Power cord (mm
2
)
3 x 1,5
3 x 1,5
3 x 1,5