ACCESSING THE TEST MENU

To access the Test Menu, 

 and 

 the hidden Next key for 7 

seconds until the fan test screen (Option 01) appears.

TOUCH

HOLD

The Test Menu is used to test the Indoor Fan Operation, Allowable 
Heating Airflow Limits and Allowable Cooling Airflow Limits.

Inside

Tu

Day

Upstairs

Auto

Downstairs

Airflow %

COOL

Schedule

AUTO

FAN

MENU

MODE

Cool

Set To

SYSTEM

AM

TOUCH

HOLD

 and 

 this key for 7 seconds

to access the Installer Options.

01-02  Testing Indoor Fan Operation

In Option 1, the Fan is Off.

Touch 

 to go to Option 2 

to turn on the indoor fan. Verify 
the fan is operating and 
delivering airflow to the 
upstairs and downstairs..

Touch 

 to go Testing 

Heating Airflow Limits.

NEXT

NEXT

Upstairs

Downstairs

Airflow %

Test

FAN

NEXT

ENTER

Upstairs

Downstairs

Airflow %

Test

FAN

NEXT

ENTER

03-04  Testing Heating Airflow Limits

In Option 3, the system is Off.

Touch 

 to go to Option 4 

to activate heating. Verify the 
equipment is operating.

To determine the maximum 
allowable upstairs airflow, 
touch the 

 key until the 

airflow is too great and causes 
noise or annoyance. Lower the 
airflow using the 

 key 

until it is acceptable. This is the 
maximum allowable upstairs 
airflow in heating. Record the 
airflow value.

NEXT

UP

DOWN

Upstairs

Downstairs

Airflow %

Test

NEXT

ENTER

Heat

Upstairs

Downstairs

Airflow %

NEXT

ENTER

Heat

This test is used to verify that the indoor fan is operating correctly.

This test is used to determine the maximum allowable upstairs airflow 
and the maximum allowable downstairs airflow in HEATING.

Maximum Allowable Upstairs Airflow in Heating

Upstairs

Downstairs

Airflow %

NEXT

ENTER

Heat

To determine the maximum 
allowable downstairs airflow, 
touch the 

 key until the 

airflow is too great and causes 
noise or annoyance. Increase 
the airflow using the 

 key 

until it is acceptable. This is the 
maximum allowable downstairs 
airflow in heating. Record the 
airflow value.

DOWN

UP

Maximum Allowable Downstairs Airflow in Heating

05-06  Testing Cooling Airflow Limits 

In Option 5, the system is Off.

Touch 

 to go to Option 6 

to activate cooling. Verify the 
equipment is operating.

To determine the maximum 
allowable upstairs airflow, 
touch the 

 key until the 

airflow is too great and causes 
noise or annoyance. Lower the 
airflow using the 

 key 

until it is acceptable. This is the 
maximum allowable upstairs 
airflow in cooling. Record the 
airflow value.

NEXT

UP

DOWN

This test is used to determine the maximum allowable upstairs airflow 
and maximum allowable downstairs airflow in COOLING.

Touch 

 to go to Testing Cooling Airflow Limits.

NEXT

Upstairs

Downstairs

Airflow %

NEXT

ENTER

Cool

Upstairs

Downstairs

Airflow %

ENTER

Cool

Maximum Allowable Upstairs Airflow in Cooling

To determine the maximum 
allowable downstairs airflow, 
touch the 

 key until the 

airflow is too great and causes 
noise or annoyance. Increase 
the airflow using the 

 key 

until it is acceptable. This is the 
maximum allowable downstairs 
airflow in cooling. Record the 
airflow value.

DOWN

UP

Maximum Allowable Downstairs Airflow in cooling

Touch 

 to end testing and return to normal thermostat 

operation.

ENTER

Upstairs

Downstairs

Airflow %

ENTER

Cool

Enter the maximum airflow limits using Options 20 
through 23 of the installer menu.

03-04  Testing Heating Airflow Limits (cont.)

Test

Test

Test

Test

NEXT

Test

NEXT

The Test Menu can also be used to perform the HERS Total Airflow 
test. Option 05-06 activates a cooling call and opens both dampers to 
100% enabling the installer to perform the test.

The test can also be used to perform the HERS Total Airflow test. The 
test activates a cooling call and opens both dampers to 100%.

Содержание C365T21

Страница 1: ...he C365 monitors the downstairs temperature The C365 adjusts the upstairs and downstairs airflow during heating and cooling calls to maintain uniform upstairs and downstairs temperatures SYSTEM MODES Off Heat Cool Auto THERMOSTAT MODES Hold Schedule or Vacant mode PROGRAMS PER DAY Morning Daytime Evening and Night PROGRAM FORMAT Weekdays and weekend 5 2 TEMPERATURE OVERRIDE Temperature is held for...

Страница 2: ...uired to define the upstairs or downstairs zones the damper may be wired in parallel LEDS on the damper actuator indicate when the damper is fully open green or fully closed red Green LED Red LED INSTALL UPSTAIRS DOWNSTAIRS DAMPERS R C WOB EQUIPMENT Y G Upstairs Sensor COM COM CLS CLS OPN OPN Upstairs Downstairs Upstairs Sensor W2E Y2 C365T21 Ensure that damper installation does not cause obstruct...

Страница 3: ...C365T21 Downstairs Thermostat Model TS5 Upstairs Temperature Sensor Model R80CT XX Downstairs Damper Y Y W O or B C C R R WIRING DIAGRAM C365T21 Upstairs Sensor WIRING INSTRUCTIONS Cont Use 3 conductor 18 or 20 gage thermostat cable to wire from the C365 Thermostat to the upstairs and downstairs dampers There are separate terminals for the upstairs and the downstairs dampers Multiple dampers can b...

Страница 4: ...n to thermostat operation CHANGE THE DAY OF THE WEEK Inside Tu Day Upstairs Auto Downstairs Airflow COOL Schedule AUTO FAN MENU MODE Cool Set To SYSTEM AM Touch here to change the time and day of the week We ENTER AM NEXT ENTER AM Press the touchscreen with your fingertip only using a firm touch Do not use a sharp object such as a pen or pencil Inside Tu Day Upstairs Auto Downstairs Airflow COOL S...

Страница 5: ...cription Equipment Type Reversing Valve Compressor Stages Compressor Minimum Off Time minutes Gas Minimum Off Time minutes Minimum Run Time minutes On Off Temperature Differential Smart Recovery Vacant Heating Setpoint Vacant Cooling Setpoint o o 0 Cooling On 1 above setpoint Off at setpoint Heating On1 below setpoint Off at setpoint o o o o 1 Cooling On 1 above setpoint Off 5 below setpoint Heati...

Страница 6: ...NEXT ENTER Touch the keys to set the time in minutes to update the upstairs and downstairs airflow Touch or UP DOWN NEXT ENTER Option NEXT ENTER This is the frequency in minutes that the damper position is updated 14 Calibrate Upstairs Temperature Sensor Factory Default None o Range 5 15 Airflow Update Time Factory Default 2 Minutes Range 1 to 20 Minutes Touch the UP DOWN keys to change the minimu...

Страница 7: ... Airflow in Cooling Factory Default 140 Range 100 to 160 22 Maximum Downstairs Airflow in Heating Factory Default 150 Range 100 to 160 23 Maximum Downstairs Airflow in Cooling Factory Default 140 Range 100 to 160 24 Maximum Temperature Differential Factory Default 2 F o Range 0 to 10 F o o 25 Factory Restore WARNING Factory Restore resets ALL settings WiFi model only When participating in Demand S...

Страница 8: ... is too great and causes noise or annoyance Increase the airflow using the key until it is acceptable This is the maximum allowable downstairs airflow in heating Record the airflow value DOWN UP Maximum Allowable Downstairs Airflow in Heating 05 06 Testing Cooling Airflow Limits In Option 5 the system is Off Touch to go to Option 6 to activate cooling Verify the equipment is operating To determine...

Отзывы: