Equipment Wiring, Heat Pump, 1 Compressor

Equipment Wiring, Heat Pump, 2-Compressor

Use 5-conductor, 18 or 20 gage, thermostat cable.

Use 5-conductor, 18 or 20 gage, thermostat cable.

C365

Terminal

C365

Terminal

R

R

C

C

WOB

WOB

Y1

Y1

G

G

W2E/Y2

W2E/Y2

Wire Color

Wire Color

Red

Red

Blue

Blue

White

White

Yellow

Yellow

Green

Green

Brown

Brown

Equipment

Terminal

Equipment

Terminal

R, Rc, Rh

R, Rc, Rh

C

C

O or B

O or B

Y, Y1

Y, Y1

G

G

W, W2 or E

Y2

Function

Function

24VAC Power

24VAC Power

Common

Common

Rev Valve

Rev Valve

Fan

Fan

Aux Heat

Stg2 Compressor

Compressor

Stg1 Compressor

R

COM

CLS

OPN

COM

CLS

OPN

C

W/OB

EQUIPMENT

Upstairs

Downstairs

Y1

G

W2E/Y2

Upstairs

Sensor

Model A80-MOC

Damper Actuator

Modulating or
Open/Close
24VAC,2.4VA

COM

OPN

CLS

Made in USA

eControls, Inc.

Model A80-MOC

Damper Actuator

Modulating or
Open/Close
24VAC,2.4VA

COM

OPN

CLS

Made in USA

eControls, Inc.

G

G

W2

Y2

GE HP

E

Y2

HVAC System

Model R80CT-XX
Upstairs Damper

Model C365T21
Downstairs Thermostat

Model TS5
Upstairs
Temperature
Sensor

Model R80CT-XX
Downstairs Damper

Y

Y

W O or B
C

C

R

R

WIRING DIAGRAM

C365T21

Upstairs
Sensor

WIRING INSTRUCTIONS (Cont)

Use 3-conductor, 18 or 20 gage, thermostat cable to wire from 
the C365 Thermostat to the upstairs and downstairs dampers. 
There are separate terminals for the upstairs and the 
downstairs dampers.

Multiple dampers can be used to construct the upstairs or 
downstairs zones.  Daisy chain terminals– COM to COM, OPN 
to OPN and CLS to CLS.

Use 2-conductor, 18 or 20 gage, thermostat cable to wire from 
the C365 Thermostat to the upstairs temperature sensor.

For single temperature sensor application, use Model TS5-10. 

Two temperature sensors can be installed in different areas 
upstairs and the two temperatures will be averaged. For dual 
sensor applications, use Model TS5-20 and daisy chain the 
sensors.  

Closes damper

Opens damper

Thermistor

Thermistor

Common

Function

Function

Upstairs Temperature Sensor Wiring  

Damper

Terminal

Sensor

Terminal

COM

SNR

CLS

SNR

OPN

Wire Color

Wire Color

Damper Wiring

White

White

Red

Red

Green

C365

Terminal

C365

Terminal

COM

SNR

CLS

SNR

OPN

Содержание C365T21

Страница 1: ...he C365 monitors the downstairs temperature The C365 adjusts the upstairs and downstairs airflow during heating and cooling calls to maintain uniform upstairs and downstairs temperatures SYSTEM MODES Off Heat Cool Auto THERMOSTAT MODES Hold Schedule or Vacant mode PROGRAMS PER DAY Morning Daytime Evening and Night PROGRAM FORMAT Weekdays and weekend 5 2 TEMPERATURE OVERRIDE Temperature is held for...

Страница 2: ...uired to define the upstairs or downstairs zones the damper may be wired in parallel LEDS on the damper actuator indicate when the damper is fully open green or fully closed red Green LED Red LED INSTALL UPSTAIRS DOWNSTAIRS DAMPERS R C WOB EQUIPMENT Y G Upstairs Sensor COM COM CLS CLS OPN OPN Upstairs Downstairs Upstairs Sensor W2E Y2 C365T21 Ensure that damper installation does not cause obstruct...

Страница 3: ...C365T21 Downstairs Thermostat Model TS5 Upstairs Temperature Sensor Model R80CT XX Downstairs Damper Y Y W O or B C C R R WIRING DIAGRAM C365T21 Upstairs Sensor WIRING INSTRUCTIONS Cont Use 3 conductor 18 or 20 gage thermostat cable to wire from the C365 Thermostat to the upstairs and downstairs dampers There are separate terminals for the upstairs and the downstairs dampers Multiple dampers can b...

Страница 4: ...n to thermostat operation CHANGE THE DAY OF THE WEEK Inside Tu Day Upstairs Auto Downstairs Airflow COOL Schedule AUTO FAN MENU MODE Cool Set To SYSTEM AM Touch here to change the time and day of the week We ENTER AM NEXT ENTER AM Press the touchscreen with your fingertip only using a firm touch Do not use a sharp object such as a pen or pencil Inside Tu Day Upstairs Auto Downstairs Airflow COOL S...

Страница 5: ...cription Equipment Type Reversing Valve Compressor Stages Compressor Minimum Off Time minutes Gas Minimum Off Time minutes Minimum Run Time minutes On Off Temperature Differential Smart Recovery Vacant Heating Setpoint Vacant Cooling Setpoint o o 0 Cooling On 1 above setpoint Off at setpoint Heating On1 below setpoint Off at setpoint o o o o 1 Cooling On 1 above setpoint Off 5 below setpoint Heati...

Страница 6: ...NEXT ENTER Touch the keys to set the time in minutes to update the upstairs and downstairs airflow Touch or UP DOWN NEXT ENTER Option NEXT ENTER This is the frequency in minutes that the damper position is updated 14 Calibrate Upstairs Temperature Sensor Factory Default None o Range 5 15 Airflow Update Time Factory Default 2 Minutes Range 1 to 20 Minutes Touch the UP DOWN keys to change the minimu...

Страница 7: ... Airflow in Cooling Factory Default 140 Range 100 to 160 22 Maximum Downstairs Airflow in Heating Factory Default 150 Range 100 to 160 23 Maximum Downstairs Airflow in Cooling Factory Default 140 Range 100 to 160 24 Maximum Temperature Differential Factory Default 2 F o Range 0 to 10 F o o 25 Factory Restore WARNING Factory Restore resets ALL settings WiFi model only When participating in Demand S...

Страница 8: ... is too great and causes noise or annoyance Increase the airflow using the key until it is acceptable This is the maximum allowable downstairs airflow in heating Record the airflow value DOWN UP Maximum Allowable Downstairs Airflow in Heating 05 06 Testing Cooling Airflow Limits In Option 5 the system is Off Touch to go to Option 6 to activate cooling Verify the equipment is operating To determine...

Отзывы: