background image

6

UNVENTED NATURAL GAS LOG HEATER

103424

AIR FOR
COMBUSTION AND
VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside
Building

This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see op-
tion 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation
 for
required size of ventilation grills or ducts.

Figure 3 - Ventilation Air from Outdoors

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANS
Z223.1, Section 5.3, Air for Combustion and
Ventilation
 for required size of ventilation
grills or ducts.

IMPORTANT:

 Do not provide openings for

inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.

Figure 2 - Ventilation Air from Inside Building

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into

Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

 WARNING: Rework work-

sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.

Содержание CGG2618N

Страница 1: ...nd Ventilation section page 4 in this manual WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do...

Страница 2: ...sed before running heater 8 This log heater is designed to be smoke less If logs ever appear to smoke turn off heater and call a qualified service person Note During initial operation slight smoking c...

Страница 3: ...ters State and local codes in some areas prohibit the use of vent free heaters Non thermostat models may also be operated as a vented decorative ANS Z21 60 product by opening flue damper SAFETY PILOT...

Страница 4: ...ion However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outsid...

Страница 5: ...rect vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________...

Страница 6: ...e two per manent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors orspacesopentotheoutdoors Thesespaces include attics and crawl spaces...

Страница 7: ...air may cause mildew to form from too much moisture See Air for Com bustion and Ventilation pages 4 through 6 CHECK GAS TYPE Use only natural gas If your gas supply is not natural gas do not install...

Страница 8: ...K No hood accessory needed Less than 8 Noncombustiblematerialmustbeextendedtoatleast8 See Between 8 and 12 above If you cannot extend material youmustoperateheaterwithfluedamperopen Figure 5 Heat Resi...

Страница 9: ...7 when using hood Mantel Shelf INSTALLATION Continued Figure 7 Minimum Mantel Clearances When Using Hood Mantel Shelf Minimum Non Combustible Material 8 Min 12 15 18 All minimum distances are in inche...

Страница 10: ...e floor If not heater will move when you adjust controls Moving heater may cause a gas leak INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION Note When used as a vented heater appli ance must be...

Страница 11: ...de a manual shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 13 Apply pipe joint sealant lightly to male t...

Страница 12: ...orrect all leaks at once WARNING Neveruseanopen flame to check for a leak Apply a mixture of liquid soap and water toalljoints Bubblesformingshow a leak Correct all leaks at once WARNING Test all gas...

Страница 13: ...ddle log 2 see Figure 18 Make sure notches on bottom rest on grate prongs 4 Finally place top log 4 over bottom middle log 2 by matching the notches under log 4 with the raised blocks of log 2 see Fig...

Страница 14: ...the front burner If needed keep press ing ignitor button until pilot lights Note If pilot does not stay lit con tact a qualified service person or gas supplier for repairs Until repairs are made light...

Страница 15: ...s heater with glassdoorsclosed Ifyouoper ate heater with doors closed heatbuildupinsidefireplacewill cause glass to burst Also if fireplace opening has vents at the bottom you must open the vents befo...

Страница 16: ...ilot does not light contact a qualified service person or gas sup plier for repairs Until repairs are made light pilot with match To light pilot with match see Manual Light ing Procedure column 3 7 Ke...

Страница 17: ...air to mix with the gas This provides a clean burning flame Keep these holesclearofdust dirt andlint Cleanthese air inlet holes prior to each heating season Blocked air holes will create soot We rec...

Страница 18: ...amaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind...

Страница 19: ...fter a few hours of operation 1 Refer to Air for Combustion and Venti lation requirements page 4 1 Turn control knob to LO position and let warm up for a minute 2 Operate burners until air is removed...

Страница 20: ...k SeeWarning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Thermostat sensing bulb needs to be r...

Страница 21: ...not mount sensing bulb until step 5 If you have a masonry fire place see Figure 33 for location If you have a factory built metal fire place see Figure 34 for location If your fireplace has glass doo...

Страница 22: ...Natural Gas Only Natural Gas Only Natural Gas Only Natural Gas Only Ignition Piezo Piezo Piezo Piezo Pressure 3 4 W C 3 4 W C 3 4 W C 3 4 W C Inlet Gas Pressure in of water Maximum 10 5 10 5 10 5 10 5...

Страница 23: ...11 Parts Department East Coast Energy Products 707 Broadway W Long Branch NJ 07764 1542 732 870 8809 1 800 755 8809 Parts Department Tarantin Tank Co P O Box 6129 Freehold NJ 07728 6129 908 780 9340 1...

Страница 24: ...AL GAS LOG HEATER 103424 ILLUSTRATED PARTS BREAKDOWN Variable Manually Controlled Models CGG2618N CGG3324N CGG3630N 18 20 19 26 25 21 21 27 5 6 7 8 29 29 25 10 9 11 12 13 15 22 23 27 1 27 2 24 7 1 7 2...

Страница 25: ...098867 09 Gas Regulator 1 13 M11084 38 M11084 38 M11084 38 Screw 2 14 101011 01 101011 02 101011 03 Inlet Tube 1 15 098354 01 098354 01 098354 01 Control Knob 1 16 098462 03 098462 03 098462 03 Contr...

Страница 26: ...ED NATURAL GAS LOG HEATER 103424 ILLUSTRATED PARTS BREAKDOWN Thermostat Controlled Model CGG3324NT 5 6 25 6 7 8 9 10 11 8 8 29 13 12 13 14 15 16 18 17 19 24 26 27 7 1 7 2 29 22 23 21 28 20 30 10 1 10...

Страница 27: ...999 05 Rear Burner Assembly 1 12 101331 08 Base Assembly with decals 1 13 098271 06 Ignitor Cable 1 14 102445 01 Piezo Ignitor 1 15 098867 09 Gas Regulator 1 16 M11084 38 Screw 2 17 102810 02 Inlet Tu...

Страница 28: ...r costs related to repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY...

Отзывы: