Comfort Glow CF26PR Скачать руководство пользователя страница 5

5

105442

OWNER’S MANUAL

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills

between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =  2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

_________________ Btu/Hr

Gas water heater*

_________________ Btu/Hr

Gas furnace

_________________ Btu/Hr

Vented gas heater

_________________ Btu/Hr

Gas fireplace logs

_________________ Btu/Hr

Other gas appliances* +

_________________ Btu/Hr

Total                            =

_________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

___________ Btu/Hr (maximum the space can support)

___________ Btu/Hr (actual amount of Btu/Hr used)

Example:

 51,200 Btu/Hr (maximum the space can support)

56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

30,000

Btu/Hr

Vent-free fireplace  +

26,000

Btu/Hr

Total                        =

56,000

Btu/Hr

Continued

Содержание CF26PR

Страница 1: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor sphone Followthegassupplier s instructions If you cannot reac...

Страница 2: ...ock and debris could fall into the control area of fireplace 8 You must operate this fireplace with the fireplace screen in place Make sure fireplace screen is in place before run ning fireplace 9 Thi...

Страница 3: ...ludes one hardware packet 4 Checkfireplaceforanyshippingdamage If fireplace is damaged promptly inform dealer where you bought fireplace PRODUCT FEATURES SAFETY PILOT This fireplace has a pilot with a...

Страница 4: ...rlesspassagewaysorventila tion grills between them WARNING This heater shall notbeinstalledinaconfinedspace or unusually tight construction unless provisions are provided foradequatecombustionandven t...

Страница 5: ...Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used ___________ Btu Hr maximum the sp...

Страница 6: ...N Continued Figure 2 Ventilation Air from Inside Building Shown with Optional Mantel VENTILATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ven...

Страница 7: ...t top or sides of the fireplace as a fireplace insert in high traffic areas in windy or drafty areas IMPORTANT Vent freefireplacesaddmois ture to the air Although this is beneficial installing firepla...

Страница 8: ...gas line to fireplace gas regulator See Connecting Fireplace to Gas Supply page 13 6 If the optional blower has been installed connect blower to electrical source Option one Route blower electrical co...

Страница 9: ...achmenttowall 9 Slide mantel around fireplace Be care ful not to damage wall or mantel Note All vertical measurements are from top of fireplace opening to bottom of mantel shelf 10 Adjust assembly to...

Страница 10: ...ss through lower opening to the left of the blower control shield see Figure 16 8 Insert the 4 wire harness into one of the round holes in the rear of the blower control shield and through the rectan...

Страница 11: ...pplied will not be used in built in installations Pop intheplasticsnapbushingfoundinhard warekitintotheholeleftbysupplycord strain relief 4 A licensed electrician must follow the wiring diagram in Fig...

Страница 12: ...n Figure 20 Pointing the vent down protects it from freezing rain or sleet Installation must include a manual shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hoo...

Страница 13: ...ssible Manual Shut Off Valve Flexible Gas Line from Fireplace Gas Valve Provided with Fireplace To Fireplace Gas Valve 2 Apply pipe joint sealant lightly to male threads of gas connector attached to f...

Страница 14: ...WARNING Neveruseanopen flame to check for a leak Apply a mixture of liquid soap and water toalljoints Bubblesformingshow a leak Correct all leaks at once CAUTION Make sure external regulator has been...

Страница 15: ...ling Receiver 1 Disconnect switch wires from the con trol valve 2 Remove screws and nuts 3 Remove switch plate see Figure 28 Discard after removing 4 Install remote receiver unit onto gas log heater b...

Страница 16: ...Volt Battery Not Included in Hand Held Remote Control Unit 1 Remove battery cover on back of re mote control unit 2 Attach terminal wires to the battery Place battery into the battery housing 3 Replac...

Страница 17: ...hand held remote ON button was on when selector switch was last turned off You can now turn the burner on and off with the hand held remote control unit IMPORTANT Do not leave the selector switch in t...

Страница 18: ...ough 22 Pilot Burner Thermocouple INSPECTING BURNERS BURNER PRIMARY AIR HOLES Air is drawn into the burner through the holes in the fitting at the burner entrance These holes may become blocked with d...

Страница 19: ...lean burning flame Keep these holesclearofdust dirt andlint Cleanthese air inlet holes prior to each heating season Blocked air holes will create soot We rec ommend that you clean the unit every 2 500...

Страница 20: ...EMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base pa...

Страница 21: ...lation requirements page 4 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Obse...

Страница 22: ...noise just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion REMEDY 1 Th...

Страница 23: ...t Cans Unlimited Inc P O Box 645 Taylor SC 29687 0013 All States 803 879 3009 1 800 845 5301 Parts Department Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 0322 1 800 397 7553 203 248 7553 Pa...

Страница 24: ...VENT FREE PROPANE LP BAY FRONT FIREPLACE CF26PR ILLUSTRATED PARTS BREAKDOWN CF26PR O F F P I L O T O N H I L O O F F P I L O T O N H I L O 16 15 19 8 19 20 21 17 18 14 13 23 10 12 22 13 4 7 6 9 5 11...

Страница 25: ...1 7 099056 21 Burner Orifice Injector 1 8 099998 01 Switch 1 9 102980 01 Burner 1 10 099387 13 Pilot Tube 1 11 103781 02 Gas Control Valve 1 12 103345 02 Lower Bracket 1 13 M11084 38 Screw 8 x 38 7 1...

Страница 26: ...26 105442 VENT FREE PROPANE LP BAY FRONT FIREPLACE CF26PR ILLUSTRATED PARTS BREAKDOWN CF26PR 5 8 15 17 13 14 11 2 11 1 21 19 4 12 16 10 6 5 9 1 2 18 7 20 2 20 3 20 1 18 18 16 22 3 18 16 3 22...

Страница 27: ...11 Rivets 8 14 105262 01CK Louvered Door 1 15 105261 01CK Firebox Floor 1 16 098304 01 Screw 10 x 3 8 21 17 105256 01CK Bayfront Bottom Panel 1 18 M11084 26 Hex Head Screws 10 x 38 26 19 105513 01CV...

Страница 28: ...te assembly instructions in cluded Three sided brass trim kit included MANUAL SHUTOFF VALVE GA5010 Manual shutoff valve with 1 8 NPT tap THERMOSTATICALLY CONTROLLED BLOWER KIT GA3450T Provides better...

Страница 29: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 30: ...ance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective fireplace will be the responsibility of th...

Отзывы: