VenTing inSTallaTion

Continued

Pitch

Slope Opening 

"A" Max. 

Used Flashing 

Model No. 

Flat

15"

V6F-8DM

0-6/12

26.6°

16 

1

/

8

"

V6F-8DM

6/12- 12/12 45.0°

20 

3

/

8

"

V12F-8DM

4.  Remove shingles around opening mea

-

sured. Cut out this section.

5.  Add  next  sections  of  pipe  until  end 

penetrates  roof  line.  Check  to  see  that 
proper clearances are maintained. Extend 
chimney by adding sections of double wall 
pipe  until  pipe  is  minimum  of  30"  above 
highest  point  of  roof  cutout.  Termination 
and chimney must extend a minimum of 
36" above highest point where it passes 
through roof.

Figure 14 - Roof Opening Measurements

FLASHING INSTALLATION (v6F-8DM 
OR v12F-8DM)

Determine flashing to be used with roof open

-

ing chart. Slide flashing over pipe until base is 
flat against roof. Replace as many shingles as 
needed to cover exposed area and flashing 
base.  Secure  in  position  by  nailing  through 
shingles (see Figure 15, page 11). DO NOT 
NAIL THROUGH FLASHING CONE.

Installing Flashing on a Metal Roof

When  installing  flashing  on  a  metal  roof,  it 
is required that putty tape be used between 
flashing and roof. Flashing must be secured 
to roof using #8 x 3/4" screws and then sealed 
with roof coating to prevent leakage through 
screw holes. A roof coating must also be ap

-

plied around perimeter of flashing to provide 
a proper seal.

FIRESTOP SPACERS (FS-8DM)

Firestop spacers are required at each point 
where  chimney  penetrates  a  floor  space. 
Their  purpose  is  to  establish  and  maintain 
required  clearance  between  chimney  and 
combustible  materials.  When  pipe  passes 
through a framed opening into a living space 
above, firestop must be placed onto ceiling 
from below as shown in Figure 12.
They also provide complete separation from 
one floor space to another or attic space as 
required  by  most  codes.  When  double  wall 
pipe passes through a framed opening into 
an attic space, firestop must be placed into 
an attic floor as shown in Figure 13.

Figure 12 - Firestop Spacer with Living 

Space Above Ceiling

Figure 13 - Firestop Spacer with Attic 

Space Above Ceiling

PENETRATING ROOF

To maintain a 2" clearance to pipe on a roof with 
a pitch, a rectangular opening must be cut.
1.  Determine  center  point  where  pipe  will 

penetrate the roof.

2.  Determine center point of the roof. Pitch 

is the distance the roof drops over a given 
span, usually 12". A 6/12 pitch means that 
the roof drops 6" for each 12" measure 
horizontally down from roof rafters.

3.  Use  roof  opening  chart  (Figure  14)  to 

determine  correct  opening  length  and 
flashing required.

If area above is a living space, install 

firestop below framed hole.

If area above is an attic or insulated area, 

install firestop above framed hole.

30"

(76.2 cm)

Minimum Measurements

Opening "A"

16 

3

/

8

"

(48.3 cm)

2"

(5.1
cm)

2"

(5.1
cm)

2"

(5.1 cm)

Содержание B42LI-M

Страница 1: ...r use with a vent free gas log heater approved to ANS Z21 11 2 standard A DESA Heating LLC hood must be installed when using a vent free log heater see Accessories page 18 This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacte...

Страница 2: ...amageor loss of life Refer to this manual for assistance or additional in formation Consult a qualified installer or local distributor IMPORTANT Check local codes before installing this fireplace Before beginning installation of this fireplace read these instructions through completely This DESA Heating LLC fireplace and its components are safe when installed ac cording to this installation manual...

Страница 3: ...PACE TO COMBUSTIBLE COMBUSTIBLE WALL BOARD 0 TO MATERIAL NO COMBUSTIBLE MATERIAL ON FACE GAS LINE KNOCK OUT AIR KIT KNOCK OUTS ROUND TOP TERMINATION GAS LINE KNOCK OUTS LEFT SIDE RIGHT SIDE NOT LESS THAN 14 TO PERPENDICULAR SIDEWALL SQUARE CHASE TOP TERMINATION 8 25 10 375 13 37 5 33 44 42 21 5 32 6 5 38 85 14 438 1 375 25 375 7 7 1 8 25 14 44 1 1 75 0 625 28 5 21 125 ...

Страница 4: ...ure ment includes fireplace chimney sections and height of termination assembly at level of flue gas outlet see Figure 18 page 11 Framing 1 Frame opening for fireplace using dimen sions shown in Figures 1 and 2 2 If fireplace is to be installed directly on carpeting tile other than ceramic or any combustible material other than wood flooring fireplace must be installed upon a metal or wood panel e...

Страница 5: ...obtained from manufacturer or supplier of noncombustible material If hearth extension is to be covered use noncombustible mate rial such as tile slate brick concrete metal glass marble stone etc Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material see Figure 3 WARNING Hearthextension is to be installed on...

Страница 6: ...ptional with this fireplace for circulating models only Use of blowers or fans other than those manufactured by DESA Heating LLC voids warranty Fan is operated by pressing rocker switch see Figure 6 in lower right hand corner of fireplace face Blower is operated by turning control knob not shown Fan blower kit electrical connections are made through electrical cover plate on side of fireplace a sh...

Страница 7: ...Installation Air Inlet Eyebrow Vented Crawl Space Check Local Codes Before Installing in a Vented Crawl Space Venting Installation Optional Outside air Kit Model AK4 AK4F Installation of outside air kit should be per formed during rough framing of fireplace due to the nature of it s location Outside combus tion air is accessed through a vented crawl space AK4F or through a sidewall AK4 See Figure ...

Страница 8: ...e obstructed Never use blown insulation to fill chimney enclosure Continue to assemble chimney sections as outlined making sure that both inner and outer pipe sections are locked together When installing double wall snap lock chimney to gether it is important to assure joint between chimney sections is locked Check by pulling chimney upward after locking Chimney will not come apart if properly loc...

Страница 9: ...60 3 4 1 1 33 66 1 1 36 71 1 1 38 1 4 75 2 41 1 4 80 1 4 1 1 1 45 86 3 4 2 46 3 4 89 1 2 1 1 1 51 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 4 111 1 2 1 1 1 61 3 4 115 1 2 2 1 64 3 4 120 3 4 2 1 68 1 4 127 1 2 70 130 2 1 1 74 1 4 137 1 2 1 2 1 76 3 4 141 1 2 1 2 1 79 3 4 146 3 4 4 OFFSET CHART 22 50 FT SYSTEM HEIGHT 2 Min Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop S...

Страница 10: ...round perimeter of flashing to provide a proper seal Firestop Spacers FS 8DM Firestop spacers are required at each point where chimney penetrates a floor space Their purpose is to establish and maintain required clearance between chimney and combustible materials When pipe passes through a framed opening into a living space above firestop must be placed onto ceiling from below as shown in Figure 1...

Страница 11: ...rmination being used Flashing Cone Venting Installation Continued Attach Bracket Tabs to Outer Pipe 3 Places Secure with Screws RTL 8DM Level of Flue Gas Outlet Caulk Collar Flashing Underlap Shingles Bottom Only Figure 17 Termination Overlap Shingles Top and Sides Terminations with 16 slip pipe sections are available RTT 8DM and RTTL 8DM are approved for flashing installations When needed these a...

Страница 12: ... contact with sides and top around fireplace face It is important that combustible materials do not overlap face itself Brick glass tile or other noncombustible materials may overlap front face provided they do not obstruct essential openings such as louvered slots When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive 30E 8DM EFFECTIVE HEIGHT OF TERMINAT...

Страница 13: ...nd refractory knockout hole with refractory cement or commercial furnace cement Install gas appliance or cap off gas line if desired CAUTION Allgaspipingand connections must be tested for leaks after installation is com pleted After ensuring that gas valveison applysoapandwater solution to all connections and joints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR...

Страница 14: ...ass Doors Glass doors are optional with this fireplace When fireplace is in operation doors must be fully opened or fully closed position only or a fire hazard may be created see Figure 23 A fireplace equipped with glass doors oper ates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Exces sive heat within fireplace can r...

Страница 15: ...grate with DESA Heating LLC model 109910 01 only This gratehasbeendesignedtokeep the operation of your fireplace safe and efficient For further operating guidelines instruc tions and warranty information please re fer to your homeowner s guide or contact your authorized dealer Damper Handle 1 2 3 1 2 3 Damper Weight To Close Damper To Open Damper Figure 25 Damper Rod Technical Service You may have...

Страница 16: ...www desatech com 115386 01B 16 Parts Wood burning Fireplace MODEL B42LI M 11 27 30 23 22 24 10 14 25 4 17 3 2 1 5 20 28 12 7 15 9 16 13 8 26 6 29 19 18 21 ...

Страница 17: ...8 Left Side Brick Liner 1 12 see page 18 Rear Brick Liner 1 13 see page 18 Right Side Brick Liner 1 14 see page 18 Bottom Brick Liner 1 15 see page 18 Front Bottom Brick Liner 1 16 21198 Blower Access Plate 1 17 20027 Refractory Retainer 2 18 109870 01 Circulation Plate 1 19 21366 Insulation Retainer 1 20 20280 Top Standoff 4 21 20023 Chimney Starter Collar 1 22 20088 Door Stop 1 23 11418 Push On ...

Страница 18: ...turn 30E 8DM Adjustable Hood Antique Brass Finish GA6053 Polished Brass Finish GA6052 Black Painted Finish GA6050 Required when installing a vent free gas log in this fireplace Storm Collar SC1 1 For RT 8DM and RTL 8DM SC1 2 For RTT 8DM and RTTL 8DM Bi Fold Glass Door BDB42 Black BDB42B Brushed Brass BDB42P Platinum Replacement Parts Standard brick liner Left 106971 01 Right 106970 01 Rear 108310 ...

Страница 19: ...inations RT 8DM RTL 8DM Round Top Terminations with Slip Section RTT 8DM RTTL 8DM Outside Air Kit for Side Wall Installation AK4 Outside Air Kit for Floor Installation AK4F Square Chase Top Termination ET 8DM ETO 8DM Econo Top Termination with Slip Section ETL 8DM ETLO 8DM Accessories Continued ...

Страница 20: ...DESA Heating LLC 2701 Industrial Drive Bowling Green KY 42101 www desatech com 1 866 672 6040 115386 01 Rev B 12 08 NOT A UPC 115386 01 ...

Отзывы: