Before connecting the thermostat, check to make sure the 

wires will be long enough for servicing at a later date. Make 

sure that thermostat wire is long enough to facilitate future 

removal of blower for service.

Complete the wiring connections to the equipment. Use the 

provided unit wiring diagram and the field wiring diagram 

shown in Figure 33. Use 18 gauge wire or larger that is 

suitable for Class II rating for thermostat connections.

Electrically ground the unit according to local codes or, in the 

absence of local codes, according to the current National 

Electric Code (ANSI/NFPA No. 70). A green ground wire is 

provided in the field make-up box.

NOTE:

 This furnace contains electronic components that 

are polarity sensitive. Make sure that the furnace is wired 

correctly and is properly grounded.

Accessory Terminals

One line voltage “EAC” 1/4” spade terminal is provided on 

the furnace integrated control. See figure 34 for integrated 

control configuration. This terminal is energized when the 

indoor blower is operating. Any accessory rated up to one 

amp can be connected to this terminal with the neutral 

leg of the circuit being connected to one of the provided 

neutral terminals. If an accessory rated at greater than one 

amp is connected to this terminal, it is necessary to use an 

external relay.

One line voltage “HUM” 1/4” spade terminal is provided on 

the furnace integrated control. See Figure 34 for integrated 

control  configuration.  This  terminal  is  energized  in  the 

heating mode when the combustion air inducer is operating. 

Any humidifier rated up to one amp can be connected to this 

terminal with the neutral leg of the circuit being connected 

to one of the provided neutral terminals. If a humidifier rated 

at greater than one amp is connected to this terminal, it is 

necessary to use an external relay relay.

Generator Use - Voltage Requirements

The following requirements must be kept in mind when 

specifying a generator for use with this equipment:

  The furnace requires 120 volts ± 10% (Range: 108 volts 

to 132 volts).

  The furnace operates at 60 Hz ± 5% (Range: 57 Hz to

 

63 Hz).

  The furnace integrated control requires both polarity 

and proper ground. Both polarity and proper grounding 

should be checked before attempting to operate the 

furnace on either permanent or temporary power.

  Generator should have a wave form distortion of less 

than 5% RHO.

Thermostat

Install the room thermostat according to the instructions 

provided with the thermostat. See Figure 31 for thermostat 

designations. If the furnace is being matched with a 

heat pump, refer to the FM21 installation instruction or 

appropriate dual fuel thermostat instructions.

Indoor Blower Speeds

1.  When the thermostat is set to “FAN ON,” the indoor 

blower will run continuously on the heating speed when 

there is no cooling or heating demand.

2.  When the unit is running in the heating mode, the indoor 

blower will run on the heating speed.

3.  When there is a cooling demand, the indoor blower will

 

run on the cooling speed.

Condensing Unit Thermostat Designations

(Refer to Specific Thermostat and Outdoor Unit.)

* Note: 

“R” Required on some outdoor units.

Figure 31

Содержание GUH80A

Страница 1: ...or equivalent service agency or the gas supplier WARNING Manufactured By Comfort Aire Century 1900 Wellworth Ave Jackson MI 49203 This manual must be left with the homeowner for future reference INST...

Страница 2: ...Return air from both sides 5 Bottom and one side return air 2 Flue outlet may be horizontal but furnace must be vented vertically 3 Optional external side return air filter kit cannot be used with th...

Страница 3: ...a licensed professional installer or equivalent service agency or the gas supplier WARNING Certifications These units are CSA International certified to ANSI Z21 47 In the USA installation of gas fur...

Страница 4: ...tions are met The vent system must be permanently installed per these installation instructions A room thermostat must control the furnace The use of fixed jumpers that will provide continuous heating...

Страница 5: ...to the house for combustion negative pressure outside pressure is greater than inside pressure will build to the point that a downdraft can occur in the furnace vent pipe or chimney As a result combus...

Страница 6: ...aining the furnace the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace This is especially important when the fur...

Страница 7: ...area of at least one square inch per 2 000 Btu 645 mm per 59 kW per hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the ai...

Страница 8: ...asher have been removed the rigid leg will not touch the blower housing Setting Equipment WARNING Do not install the furnace on its front or its back Do not connect the return air ducts to the back of...

Страница 9: ...ity See Figure 9 2 Single side return air with optional return airbase See Figure 10 3 Bottom return air 4 Return air from both sides 5 Bottom and one side return air Figure 9 Single Side Return Air w...

Страница 10: ...rs or ceiling joists When straps are used to suspend the unit in this way support must be provided for both the ends The straps must not interfere with the plenum or exhaust piping installation Coolin...

Страница 11: ...wn the vent pipe and into the room This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas This toxic gas might then be distributed throughout th...

Страница 12: ...from 9 to 5 to avoid interference with inducer motor Mounting Screws Location Figure 15 Figure 16 UPFLOW POSITION Top Vent Discharge The combustion air inducer may be rotated clockwise or counterclock...

Страница 13: ...ng must be brought into the unit from the bottom in order to accommodate the flue pipe Cut combustion air inducer tubing from 9 to 8 to avoid interference with inducer motor Remove make up box assembl...

Страница 14: ...s WARNING Use self drilling sheet metal screws or a mechanical fastener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the vent pi...

Страница 15: ...ey Never connect a Category I appliance to a chimney that is servicing a solid fuel appliance If a fireplace chimney flue is used to vent this appliance the fireplace opening must be permanently seale...

Страница 16: ...etween sections of single wall connector piping shall be fastened by screws or other approved means 13 When the vent connector used for Category I appliances must be located in or pass through a crawl...

Страница 17: ...onfigureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbo...

Страница 18: ...Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving...

Страница 19: ...problem is found during any of the preceding tests the common venting system must be modified to correct the problem Resize the common venting system to the minimum vent pipe size determined by using...

Страница 20: ...Configurations NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET Figure 27 NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET Figure 26 Table 6 Gas Pipe Capacity ft hr m hr Note Capacity...

Страница 21: ...ice to protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace the control and the technician at the same electrosta...

Страница 22: ...on This terminal is energized in the heating mode when the combustion air inducer is operating Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit...

Страница 23: ...507713 01 Page 23 of 32 Issue 1623 Wiring Diagram Figure 32 045 3 135 5 110 5 110 4 110 3 090 4 090 3 070 3 070 2...

Страница 24: ...l The control stores the last 5 fault codes in non volatile memorty The most recent fault code is flashed first the oldest fault code is flashed last There is a 2 second pause between codes When the p...

Страница 25: ...exactly a fire or explosion may result causing property damage personal injury or death WARNING 6 Move switch on gas valve to OFF Do not force See Figure 35 7 Wait five minutes to clear out any gas If...

Страница 26: ...accurate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap Remove t...

Страница 27: ...red at the pressure switch under steady state conditions after 15 minutes of run time against the as shipped switch set point Insufficient negative pressure may lead to nuisance pressure switch trips...

Страница 28: ...heat anticipator setting if adjustable according to the amp draw listed on the wiring diagram that is attached to the unit NOTE Do not secure the electrical conduit directly to the air ducts or struct...

Страница 29: ...rrectly Verify proper operation after servicing WARNING At the beginning of each heating season a qualified technician should check the system as follows Blower Check the blower wheel for debris and c...

Страница 30: ...ate All service must be performed by a licensed professional installer or equivalent service agency or gas supplier Heating Parts Flame sensor Heat exchanger assembly Gas manifold Combustion air induc...

Страница 31: ...1 1535 1469 1363 1257 1158 Med High 1420 1410 1368 1314 1273 1183 1103 1002 Med 1171 1168 1150 1126 1084 1022 935 817 Low 973 978 957 927 908 840 784 680 090B4 1 2 4 spd 10 x 10 30 60 High 1911 1840 1...

Страница 32: ...mum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less t...

Отзывы: