background image

507868-02P

Page 48 of 48

Issue 1922

Requirements for Commonwealth of Massachusetts

Modifications to NFPA-54, Chapter 10

Revise NFPA-54 section 10.8.3 to add the following 

requirements:

For all side wall, horizontally vented, gas-fueled equipment 

installed  in  every  dwelling,  building  or  structure  used  in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven (7) 

feet above the finished grade in the area of the venting, 

including but not limited to decks and porches, the following 

requirements shall be satisfied:

1. 

INSTALLATION OF CARBON MONOXIDE 

DETECTORS

. At  the  time  of  installation  of  the  side 

wall,  horizontally  vented,  gas-fueled  equipment,  the 

installing  plumber  or  gas  fitter  shall  observe  that  a 

hard-wired  carbon  monoxide  detector  with  an  alarm 

and battery backup is installed on the floor level where 

the gas equipment is to be installed. In addition, the 

installing  plumber  or  gas  fitter  shall  observe  that  a 

battery-operated  or  hard-wired  carbon  monoxide 

detector with an alarm is installed on each additional 

level of the dwelling, building or structure served by the 

side wall, horizontally vented, gas-fueled equipment. 

It shall be the responsibility of the property owner to 

secure the services of qualified licensed professionals 

for  the  installation  of  hard-wired  carbon  monoxide 

detectors.

a.  In  the  event  that  the  side  wall,  horizontally 

vented,  gas-fueled  equipment  is  installed  in  a 

crawl  space  or  an  attic,  the  hard-wired  carbon 

monoxide detector with alarm and battery backup 

may be  installed on the next adjacent floor level.

b.  In the event that the requirements of this subdivision 

cannot  be  met  at  the  time  of  completion  of 

installation, the owner shall have a period of thirty 

(30) days to comply with the above requirements; 

provided,  however,  that  during  said  thirty  (30) 

day  period,  a  battery-operated  carbon  monoxide 

detector with an alarm shall be installed.

2. 

APPROVED CARBON MONOXIDE DETECTORS. 

Each  carbon  monoxide  detector  as  required  in 

accordance  with  the  above  provisions  shall  comply 

with NFPA 720 and be ANSI/UL 2034 listed and IAS 

certified.

3. 

SIGNAGE

. A metal or plastic identification plate shall 

be permanently mounted to the exterior of the building 

at  a  minimum  height  of  eight  (8)  feet  above  grade 

directly in line with the exhaust vent terminal for the 

horizontally  vented,  gas-fueled  heating  appliance  or 

equipment. The sign shall read, in print size no less 

than one-half (1/2) inch in size, “

GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.

4. 

INSPECTION

. The state or local gas inspector of the 

side  wall,  horizontally  vented,  gas-fueled  equipment 

shall  not  approve  the  installation  unless,  upon 

inspection,  the inspector  observes  carbon  monoxide 

detectors and signage installed in accordance with the 

provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is exempt 

from 24 CMR 5.08(2)(a) 1 through 4:

1.  The equipment listed in Chapter 10 entitled “Equipment 

Not Required to Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and

2.  Product Approved side wall, horizontally vented, gas-

fueled  equipment  installed  in  a  room  or  structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM PROVIDED. 

When  the  manufacturer  of  Product  Approved  side  wall, 

horizontally  vented,  gas-fueled  equipment  provides  a 

venting  system  design  or  venting  system  components 

with  the  equipment,  the  instructions  provided  by  the 

manufacturer  for  installation  of  the  equipment  and  the 

venting system shall include:

1.  Detailed instructions for the installation of the venting 

system design or the venting system components: and 

2.  A complete parts list for the venting system design or 

venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM NOT PROVIDED. 

When  the  manufacturer  of  Product  Approved  sidewall, 

horizontally  vented,  gas-fueled  equipment  does  not 

provide the parts for venting the flue gases, but identifies 

“special venting systems,” the following requirements shall 

be satisfied by the manufacturer:

1.  The referenced “special venting system” instructions 

shall  be  included  with  the  appliance  or  equipment 

installation instructions; and

2.  The  “special  venting  systems”  shall  be  Product 

Approved by the Board, and the instructions for that 

system shall include a parts list and detailed installation 

instructions.

A copy of all installation instructions for all Product 

Approved side wall, horizontally vented, gas-fueled 

equipment, all venting instructions, all parts lists 

for venting instructions, and/or all venting design 

instructions shall remain with the appliance or 

equipment at the completion of the installation.

Содержание GDD92C

Страница 1: ...or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical equipment personal injur...

Страница 2: ...507868 02P Page 2 of 48 Issue 1922 Unit Dimensions Capacity A B C in mm in mm in mm 045 B3 070 B3 17 1 2 446 16 3 8 416 16 406 090 C4 21 533 19 7 8 504 19 1 2 495...

Страница 3: ...Heating Compartment Access Panel Blower Access Panel Cold End Header Box Control Box includes integrated control transformer and door switch Blower Assembly Bag Assemblies Cabinet Blower Deck Heat Ex...

Страница 4: ...aded street elbow Check equipment for shipping damage If you find any damage immediately contact the last carrier Please refer to specification sheets for available accessories Safety Information DANG...

Страница 5: ...must be equipped to prevent operation of either the heating or the cooling unit unless it is in the full HEAT or COOL setting When installed this furnace must be electrically grounded according to lo...

Страница 6: ...re drafts might blow directly into it This could cause improper combustion and unsafe operation When the furnace is installed in a non direct vent applications do not block the furnace combustion air...

Страница 7: ...ombustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space Unconfined Space An unconfined space is an area such as a basement or large equipment...

Страница 8: ...n of rectangular air ducts shall be no less than 3 inches 75 mm In calculating free area the blocking effect of louvers grilles or screens must be considered If the design and free area of protective...

Страница 9: ...ined Space all Air from Outside Shipping Bolt Removal Units with 1 2 hp and 3 4 hp blower motors are equipped with three flexible legs and one rigid leg The rigid leg is equipped with a shipping bolt...

Страница 10: ...Do not drag the unit across the floor in the downflow position Floor and furnace flange damage will result Refer to Figure 14 for clearances in downflow applications Improper installation of the furna...

Страница 11: ...2 After opening is cut set the combustible flooring base into opening 3 Check fiberglass strips on the combustible flooring base to make sure they are properly glued and positioned 4 Lower supply air...

Страница 12: ...external static pressure which exceeds 0 5 inches w c Operation at these conditions may result in improper limit operation Supply Air Plenum If the furnace is installed without a cooling coil a remov...

Страница 13: ...ces of ignition Do not use excessive amounts of solvent cement when making joints Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors Avoid contact...

Страница 14: ...s Termination kits 44W92 and 44W93 are approved for use in Canadian installations to meet CSAB149 The 44W92 Concentric kit is provided with a 1 1 2 accelerator which must be installed on the exhaust o...

Страница 15: ...condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building...

Страница 16: ...om outdoors and flue gases are discharged outdoors Intake and exhaust pipe sizing Size pipe according to Table 6 and Table 7A through Table 7B Table 6 lists the minimum vent pipe lengths permitted Tab...

Страница 17: ...13 97 97 78 8 26 11 60 45 n a 92 92 73 9 21 n a 55 40 87 87 68 10 16 50 35 82 82 63 Concentric Termination Elevation 0 10 000 ft Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Model Mode...

Страница 18: ...60 67 67 48 10 6 40 55 62 62 43 NOTE Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation Figure 23 Typical Exhau...

Страница 19: ...the furnace from the surrounding space the indoor air quality must be considered Guidelines listed in Combustion Dilution and Ventilation Air section must be followed Follow the next two steps when i...

Страница 20: ...r to Outside Roof Terminated Exhaust Pipe Furnace Ventilation Louvers Crawl Space Intake Debris Screen Provided Inlet Air Minimum 12 in 305mm above Crawl Space Floor Coupling or 3 in to 2 in Transitio...

Страница 21: ...n in Unconditioned Space for Winter Design Temperatures Single Stage High Efficiency Furnace Winter Design Temperatures1 F C Vent Pipe Diameter Unit Input Size 045 070 090 32 to 21 0 to 6 PVC 2 PP PVC...

Страница 22: ...ce under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appl...

Страница 23: ...mm for appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for appliances 10 000 Btuh 3kw 12 inches 305mm for appliances 10 000 Btuh 3kw and 100 000 Btuh 30k...

Страница 24: ...tion is 3 76 mm on roof terminations and 6 152 mm on side wall terminations 3 On roof terminations the intake piping should terminate straight down using two 90 elbows see Figure 31 4 Exhaust piping m...

Страница 25: ...t Furnished CLAMP INTAKE 12 305mm FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT DIFFERENT VENT PIPE SIZE TO TERMINATION Figure 36 Direct Vent Concentric Wall Termination DIRECT VENT CONCENTRIC WALL...

Страница 26: ...n tee should be connected to the 2 or 3 PVC flue pipe as shown in the illustration Do not use an accelerator in applications that include an exhaust termination tee The accelerator is not required 2 A...

Страница 27: ...pipe size must be done after the final elbow Figure 40 Non Direct Vent Roof Termination Kit UNCONDITIONED ATTIC SPACE 3 76MM OR 2 51MM PVC PROVIDE SUPPORT FOR EXHAUST LINES 12 305MM ABOVE AVE SNOW ACC...

Страница 28: ...ermination Drain Trap assembled Figure 44 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure...

Страница 29: ...ondensate drain Tubing must be 1 1 4 ODx1 ID and should be attached to the drain on the trap using a hose clamp Figure 47 Condensate Trap and Plug Locations 5 Figure 49 shows the furnace and evaporato...

Страница 30: ...507868 02P Page 30 of 48 Issue 1922 Figure 49 Evaporator Coil Using a Separate Drain Figure 50 Evaporator Coil Using a Common Drain Figure 51 Condensate Trap with Optional Overflow Switch...

Страница 31: ...507868 02P Page 31 of 48 Issue 1922 Figure 52 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC...

Страница 32: ...ip leg in vertical pipe runs to serve as a trap for sediment or condensate 5 A 1 8 N P T plugged tap or pressure post is located on the gas valve to facilitate test gauge connection See Figure 53 6 In...

Страница 33: ...4 118 3 34 110 3 11 103 2 92 1 25 4 1 049 26 645 680 19 25 465 13 17 375 10 62 320 9 06 285 8 07 260 7 36 240 6 80 220 6 23 205 5 80 195 5 52 1 1 4 31 75 1 380 35 052 1400 39 64 950 26 90 770 21 80 66...

Страница 34: ...long enough to facilitate future removal of blower for service Complete the wiring connections to the equipment Use the provided unit wiring diagram and the field wiring diagram shown in Figure 58 Us...

Страница 35: ...ly on the heating speed when there is no cooling or heating demand See Table 16 for allowable continuous circulation speeds 2 When the furnace is running in the heating mode the indoor blower will run...

Страница 36: ...507868 02P Page 36 of 48 Issue 1922 045B3 070B3 090C4 Figure 59 Typical Wiring Diagram...

Страница 37: ...next to the floor because some gas is heavier than air and will settle on the floor The gas valve on the unit is equipped with a gas control switch lever Use only your hand to move switch Never use to...

Страница 38: ...low the gas supplier s instructions If you do not smell gas go to next step 8 Move gas valve switch to ON See Figure 61 9 Replace the heating compartment access panel 10 Turn on all electrical power t...

Страница 39: ...rt unit and allow 5 minutes for unit to reach steady state 3 While waiting for the unit to stabilize observe the flame Flame should be stable and should not lift from burner Natural gas should burn bl...

Страница 40: ...Orifice Kit All 11K50 73W80 51W01 11K45 Conversion requires installation of a gas valve regulator spring which is provided with the gas conversion Kit LP Kits include low line pressure switch Pressur...

Страница 41: ...2 Visually inspect the venting system for proper size and horizontal pitch Determine there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condition 3...

Страница 42: ...nticipator setting if adjustable according to the amp draw listed on the wiring diagram that is attached to the unit Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage...

Страница 43: ...65 276 1140 202 860 109 700 73 0 20 1345 360 1240 285 1090 208 810 119 645 79 0 30 1325 371 1215 291 1060 218 770 124 590 84 0 40 1295 380 1175 302 1025 228 710 132 530 91 0 50 1260 392 1135 318 985 2...

Страница 44: ...nsure proper furnace operation Table 3 lists recommended filter sizes Exhaust and Air Intake Pipes Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no...

Страница 45: ...abinet Remove two screws from blower rail which secure bottom heat exchanger flange Remove heat exchanger from furnace cabinet 17 Back wash heat exchanger with soapy water solution or steam If steam i...

Страница 46: ...ent will be displayed first LED off for 3 sec then next error code is displayed etc To clear error codes depress and hold button longer than 5 seconds Cleaning the Burner Assembly 1 Turn off electrica...

Страница 47: ...blems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Si...

Страница 48: ...height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...

Отзывы: