COMFORT-AIRE Century RSG13 Скачать руководство пользователя страница 3

507708-01

Page 3 of 9

Issue  1337

Accumulation of water and ice in base pan may cause 

equipment damage.

  CAUTION

Elevate Unit

  Elevate unit per local climate and code requirements 

to provide clearance above estimated snowfall level and 

ensure adequate drainage of unit. Use snow stand in  

areas where prolonged freezing temperatures are  

encountered.

  If conditions or local codes require the unit be  

attached to pad or mounting frame, tie down bolts should 

be used and fastened through knockouts provided in unit 

base pan.

Roof Top Installations

  Mount on level platform or frame 6 inches above roof 

surface. Place unit above a load-bearing wall and isolate 

unit and tubing set from structure. Arrange supporting 

members to adequately support unit and minimize  

transmission of vibration to building. Ensure roof structure 

and anchoring method is adequate for location. Consult 

local codes governing rooftop applications.

NOTE

:  Unit must be level to within ± 2° (± 3/8 in./ft) per 

compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow 

 

clearance, wiring, refrigerant piping, and service. For 

proper airflow, quiet operation and maximum efficiency. 

 

Position so water, snow, or ice from roof or eaves cannot 

fall directly on unit.

DO  NOT LOCATE THE UNIT:

 

•  On brick, concrete blocks or unstable surfaces 

•  Near clothes dryer exhaust vents 

•  Near sleeping area or near windows 

•   Under eaves where water, snow or ice can fall 

directly on the unit

 

•  With clearance less than 2 ft. from a second uni

 

•  With clearance less than 4 ft. on top of unit

Indoor Coil Piston Selection

  The outdoor section must be matched to a factory 

approved indoor section. It is mandatory that the installer 

ensure that the correct piston or TXV is installed in the 

indoor section. If necessary remove the existing piston 

and replace it with the correct piston or TXV. See indoor 

unit instructions for details of changing the piston or TXV. 

Contact your distributor for accessory piston kits.

  The correct piston size is shipped with the outdoor 

unit, and also listed in the specification sheet. Do not 

use the piston that comes with the indoor unit, unless it 

matches the one listed on the outdoor unit.

Refrigeration Line Sets

  Use only refrigeration grade copper tubes. Split sys-

tems may be installed with up to 50 feet of line set (no 

more than 20 feet verticle) without special consideration 

(see long line set guide lines).

DO  LOCATE THE UNIT:

 

•   With proper clearances on sides and top of unit (a 

minimum of 12” on the three sides, service side 

should be 24” and 48” on top

 

•  On  solid, level foundation or pad

 

•  To minimize refrigerant line lengths

Model

13 SEER

14 SEER

Liquid 

Line

Suction 

Line

Liquid 

Line

Suction 

Line

18

3/8 or 1/4

1

5/8

2

3/8

3/4

24

3/8 or 1/4

1

5/8

2

3/8

3/4

30

3/8

3/4

3/8

3/4

36

3/8

3/4

3

3/8

7/8

42

3/8

3/4

3

3/8

7/8

48

3/8

7/8

3/8

7/8

60

3/8

7/8

4

3/8

1 1/8

* Fittings should be supplied by the installer.
1.  For lines 25 Ft or over, use 3/8”
2.  For lines 25 Ft or over, use 3/4”
3.  For lines 25 Ft or over, use 7/8”
4.  For lines 25 Ft or over, use 1 1/8”

  Do not leave the lines open to the atmosphere for any 

period of time, moisture, dirt and bugs may contaminate 

the lines.

Содержание Century RSG13

Страница 1: ...tion and Canadian Electrical Code Part 1 CSA WARNING Safety Precautions 2 Unit Location Installation 2 Rooftop Installation Recommendations 3 Indoor Coil Piston Selection 3 Refrigeration Line Sets 3 Installation of Line Sets 4 Leak Check 4 Evacuating Charging 4 P507708 01 TABLE OF CONTENTS Electrical Connections 5 Control Wiring 5 Start Up Procedure 5 Adjusting charge 5 Single Phase Wiring Diagram...

Страница 2: ... In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refigerant tubes as directly as possible by avoiding unecessary turns and bends 4 Leave some slack b...

Страница 3: ...ance less than 2 ft from a second uni With clearance less than 4 ft on top of unit Indoor Coil Piston Selection The outdoor section must be matched to a factory approved indoor section It is mandatory that the installer ensure that the correct piston or TXV is installed in the indoor section If necessary remove the existing piston and replace it with the correct piston or TXV See indoor unit instr...

Страница 4: ... for leaks after brazing and before evacuation The recommended procedure is to apply a trace amount of vapor refrigerant approximately two ounces or 3 psig into the line set and indoor coil then pressurize with 150 psig of dry nitrogen Use a refrigerant leak detector to check all joints The system may also be checked for leaks using a halide torch or pressure and soapy solution After completion of...

Страница 5: ... wire to ground connection in control box for safety Connect power wiring to contactor High voltage power connections to 3 phase models is made to Pig Tail leads with field supplied splice connectors Contol Wiring The control voltage is 24 VAC NEC Class I insulated 18 AWG is required for control wiring For lengths longer than 150 feet contact your local distributor for technical service Ensure the...

Страница 6: ...its with Indoor TXV Units installed with cooling mode TXV require charging with the subcooling method 1 Operate unit a minimum of 10 minutes before checking charge 2 Measure liquid service valve pressure by attaching an accurate gage to service port Determine saturation temp from T P chart 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liqui...

Страница 7: ...507708 01 Page 7 of 9 Issue 1337 534773W A C SINGLE PHASE WIRING DIAGRAM Single speed condenser fan ...

Страница 8: ...Page 8 of 9 507708 01 Issue 1337 A C SINGLE PHASE WIRING DIAGRAM Multi speed condenser fan 537511 01 ...

Страница 9: ...rees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and cause damage to the condenser Periodically debris should be brushed from the condenser coils SHARP OBJECT HAZARD WARNING Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODILY INJURY Use a...

Отзывы: