A microamp DC meter is needed to check the flame signal
on the integrated control.
Flame (microamp) signal is an electrical current which
passes from the integrated control to the sensor during
unit operation. Current passes from the sensor through the
flame to ground to complete a safety circuit.
Primary Limit Control (Figure 7)
The primary limit on
GUH80C
units is located in the
heating vestibule panel under the combustion air
inducer. See Figure 7. When excess heat is sensed
in the heat exchanger, the limit will open. If the limit is
open, the integrated control energizes the supply air
blower and closes the gas valve. The limit
automatically resets when unit temperature returns to
normal. The switch must reset within three minutes or
SureLight
®
control will go into Watchguard for one
hour. The switch is factory set and cannot be adjusted.
The switch may have a different setpoint for each unit
model number.
Figure 7. Primary Limit Under Combustion Air Inducer
Primary
Limit
The
GUH80C
uses an internally redundant valve to assure
safety shut-off. If the gas valve must be replaced, the same
type valve must be used.
24VAC terminals and valve switch are located on the
valve. All terminals on the gas valve are connected to wires
from the integrated control. 24V applied to the terminals
energizes the valve.
Inlet and outlet pressure taps are located on the valve. A
regulator adjustment screw is located on the valve.
LPG changeover kits are available from
Comfort-Aire/Century
.
Kits include burner orifices and a gas valve regulator spring.
To Measure Flame Signal - Integrated Control:
Use a digital readout meter capable of reading DC
microamps. See Figure 8 for flame signal check.
1.
Set the meter to the DC amps scale.
2.
Turn off supply voltage to control.
3.
Remove sensor wire from integrated control.
4.
Connect (-) lead to flame sensor wire.
5.
Connect (+) lead to Terminal FS on integrated control.
6.
Turn supply voltage on and close thermostat contacts
to cycle system.
7.
When main burners are in operation for two minutes,
take reading.
Flame Signal in Microamps
Normal
Low
Drop Out
≥ 1.5
0.5 - 1.4
≤ 0.4
Table 6.