background image

 

IE-SNC-T2114-03 

Typical application wiring 

Calculation of minimum power voltage Uss for proper 
operation:   
 

 

Uss min > Uo +Imax*Rz, 

 
 

where: Uo = 9 V 

 

 

Imax... about 20 mA 

 

 

Rz...sensing resistor (shunt)) 

 
 

LCD Info mode 

It  is  possible  to  check  stored  output  scale  without  using  of  computer.  It  is  necessary  to  have 

connected current loop I1 (device is powered throw loop). 

Unscrew  the  transducer  lid  and  shortly  press  button  between  display  and  interconnection 

terminals by means of a tool (e.g. screwdriver). 

 

It  shows  preset  value  of  pressure  for  current  output  I1.  Lower  LCD  line 
shows  current  value  (at  mA)  which  is  associated  to  the  lowest  pressure 
output  (value  displayed  at  upper  LCD  line).  Here  4 mA  corresponds  to 
800 hPa. 
 
Press button again to get value for upper point similarly as at previous point. 
Here 20 mA corresponds to 1100 hPa. 
 

 

Notice:

 during info mode no measurement and no output current generation 

proceed. The device stays at info mode 15 s and then automatically goes back to measuring cycle. 

 
 
 

Readings on LCD display 

hPa, PSI, inHg,  

Reading next to this symbol is measured pressure or error state of value. If selected pressure unit is 

mBar 

or

  oz/in

2

  or

  mmHg

  or

  inH

2

O

  or 

kPa

,  there  is  shown  only  value  (number)  without 

corresponding pressure unit! 

 

symbol

 3 

near by left display margin

 

Is on if jumper is closed. 
 
 

Technical parameters: 

Power: 9 to 30 V dc

, maximum ripple 0.5 %

 

Measuring parameters: 

Atmospheric pressure: 

 

 

Содержание T2114

Страница 1: ...turer reserves the right to make technical changes to the device without previous notice Misprints reserved Manufacturer is not responsible for damages caused by using the device in conflict with this manual To damages caused by using the device in conflict with this manual cannot be provide free repairs during the warranty period Read carefully instruction manual before the first device connectio...

Страница 2: ...f special setting was not required in the order device is set from the manufacturer to the following parameters value at output I1 4 20 mA corresponds to atmospheric pressure from 800 to 1100 hPa1 correction for altitude 0 hPa absolute pressure display switched ON pressure unit hPa Modification of the setting is possible to do by means of the PC using procedure described at the end of this documen...

Страница 3: ...side Electrical system wiring may do only worker with required qualification by rules in operation Setting of pressure correction for altitude If there is necessary to read value of atmospheric pressure corrected with respect to altitude it is possible to set corresponding pressure offset for this altitude It is possible to do it with Users software This value is then automatically added to measur...

Страница 4: ...ted to the lowest pressure output value displayed at upper LCD line Here 4 mA corresponds to 800 hPa Press button again to get value for upper point similarly as at previous point Here 20 mA corresponds to 1100 hPa Notice during info mode no measurement and no output current generation proceed The device stays at info mode 15 s and then automatically goes back to measuring cycle Readings on LCD di...

Страница 5: ...ering from the top side Electromagnetic compatibility complies EN 61326 1 Not allowed manipulations It is not allowed to operate the device under other than specified conditions in technical parameters Devices are not designed for locations with chemically aggressive environment Do not use the device in an explosive environment Storing conditions temperature 30 to 80 C humidity 0 to 100 RH without...

Страница 6: ...ocedure to device s memory occurred or if damage of calibration data appeared At this state device does not measure and calculate values It is a serious error contact distributor of the device to fix Error 2 There is a reading Err2 on LCD display Atmospheric pressure measurement error occurred Output value is about 3 8 mA Measured pressure value with added correction for altitude is outside of ran...

Страница 7: ...IE SNC T2114 03 7 Appendix A ...

Отзывы: