7

To fully understand the system, it is vital to grasp what happens when a button is pressed or released (digital input closed or 

opened); every time there is a change to an input, the corresponding module sends a message over the bus which, as mentioned 

previously, can be destined for various recipients: 

- a module and one or more of the outputs on it

- a group

- the system manager

If the recipient is a module, its serial number and one or more of the outputs involved should be indicated, while if it is a group, its 

identification number should be indicated. Finally, if the recipient is a system manager, nothing else has to be indicated, as it is 

always open to bus communication and will receive the command originating from the module, applying for example a programmed 

scenario. 

The type of command transmitted by a module can be classified as follows:

NORMAL

: the output(s) receive the message and, if it is compatible with their profile, are activated, otherwise their status does 

not change; 

SET or RESET

: the recipient output(s) are forced into action, regardless of how they are programmed, so if a RESET command 

is sent, the output(s) are de-energised.

Analogue inputs, on the other hand, can perform the following functions:

-

 ONLY ON DEMAND

:the module constantly reads and logs the input value (converted into a scale from 0 to 255), only sending 

it when requested (by a system manager, for example);

SEND STATUS AUTOMATICALLY

: the module constantly reads and logs the input value (converted into a scale from 0 to 255), 

sending it at regular intervals as specified;

AUTOMATIC ACTIVATION ON SETPOINTS

: if this function is used, up to 8 setpoints can be selected, meaning that when the 

measured value exceeds or falls below these values a message is sent to a module/output, a group or the system manager, as 

if it were a digital module;

BCD ROOM THERMOSTAT

: this function is suitable for temperature sensor (20046708) connection, for the correct reading 

of the value in degrees Centigrade. At each pre-set time interval, the module checks the difference between the measured 

value (with a resolution of 0.1°C) and the selected setpoint (summer/winter, day/night/room empty) and sends the activation or 

deactivation command to a module/output.

DIGITAL AND ANALOGUE OUTPUT OPERATING PRINCIPLE

Each digital output has a function associated with it. When an output receives a "Normal" message from an input, it carries out the 

programmed function; otherwise, if it receives a forced command (SET or RESET), it carries out that command regardless of the 

function for which it was configured. Being multifunctional modules, different types of output are available on a programming level.

DIGITAL OUTPUT TYPES

MONOSTABLE

When the output receives an active input status (e.g. button pressed) it is activated, when it receives an 

inactive input status it is deactivated (e.g. doorbell or bathroom pull-cord).

STEP BY SETP

When the output receives an active input status (e.g. button pressed), it changes its own status in turn. 

If it receives an inactive input status, it does not make any changes (e.g. lights). This type of output can 

only be controlled by buttons.

INVERTER

When the output receives a message from the input, regardless of whether it is an input active or inactive 

message, it changes status (e.g. lights). 

N .B . This type of output allows use of the bistable function if the command originates from 

switches, diverters or inverters already present in the system instead of from buttons . 

TIMED

When the output receives an input active status, it is in turn activated, starting a timer; when the set time 

has elapsed, it is deactivated automatically. If it receives an inactive input status, it does not make any 

changes (e.g. timed stair lights or boxes). 

N .B . This type of output can only be controlled by buttons .

DIGITAL AND ANALOGUE INPUT OPERATING PRINCIPLE

Содержание 20003150

Страница 1: ...EN SYSTEM MANUAL Comelit Home Automation SimpleHome...

Страница 2: ...t as power cables 230V or higher To ensure Comelit products are used safely carefully observe the indications provided in the manuals instruction sheets make sure the system created using Comelit prod...

Страница 3: ...MODULE 19 ART 20046604 SIMPLEHOME MODULE WITH 5 OPTICALLY COUPLED INPUTS AND 4 X 16A RELAY OUTPUTS ON DIN RAIL 5I4O16A 23 ART 20046605 SIMPLEHOME MODULE WITH 9 OPTICALLY COUPLED INPUTS AND 8 X 6A RELA...

Страница 4: ...total cost The system power supply is provided by 24 Vdc 2A DIN bar power supply units which can be fitted in parallel and therefore distributed freely along the entire bus meaning the bus sections c...

Страница 5: ...of the power supply units experiences a fault Establishing the required cross sections To reduce the cross section of the bus backbones in use we recommend that power supply units are distributed as c...

Страница 6: ...nally DIN rail modules differ in terms of relay power 6A or 16A and due to the fact that the 6A modules use relays with NO normally open contact and a common every 4 outputs while 16A modules use volt...

Страница 7: ...gital module BCD ROOM THERMOSTAT this function is suitable for temperature sensor 20046708 connection for the correct reading of the value in degrees Centigrade At each pre set time interval the modul...

Страница 8: ...ia the Comelit App in conjunction with Comelit Hub module 20003150 and web pages in conjunction with Serial Bridge module 20003101 the systems can also be controlled using the main voice assistants DI...

Страница 9: ...put current 2A max Parallel connection yes Protection against reverse polarity fuse on input circuit protecting against overloads and short circuits with automatic reset function Indicator contacts 1...

Страница 10: ...ve 24 Vdc bus power supply FAIL NC contact power supply failure indication Earth L Power supply phase 230 Vac N Power supply neutral 230 Vac Earth terminal connection may cause disturbance on the comm...

Страница 11: ...4 1 optically coupled digital type Max input cable length 25 m Protection against reverse polarity Indications 1 indicator LED when flashing indicates data transmission via bus when lit steadily indic...

Страница 12: ...ristics Power supply voltage 24 Vdc 5 Absorption min 5 mA max 22 mA Inputs 4 1 optically coupled digital type Outputs 4 transistor 24 Vdc 50 mA max per output Max input cable length 25 m Protection ag...

Страница 13: ...NNECTION TERMINALS Term Function BUS power supply negative BUS power supply 24 Vdc D Bus data line V Support negative outputs O4 Output 4 O3 Output 3 O2 Output 2 O1 Output 1 I4 Input 4 I3 Input 3 I2 I...

Страница 14: ...lay control common 6 Relay control 24 Vdc Technical characteristics Power supply voltage 24 Vdc 5 Absorption 18 mA Inputs 2 for interfacing with two open collector outputs for input output modules on...

Страница 15: ...5 Connection example for module with 5 inputs 4 transistor outputs used to control an automated rolling shutter raise common lower green bus red blue Specifications are subject to change without notic...

Страница 16: ...ut cable length 2 m Protection against reverse polarity Indications 1 bus status indicator LED when flashing indicates data transmission via bus when lit steadily indicates lack of power supply negati...

Страница 17: ...17 Temperature sensor 20046708 connection example green bus red blue TEMPERATURE SENSOR 20046708 DEVICE TEMPERATURE MEASURING SENSOR Specifications are subject to change without notice...

Страница 18: ...0 bit reading resolution 0 25 C Positioning in flush mounted boxes Applicable standards electromagnetic compatibility EN 50081 1 interference emission and EN50082 2 resistance to interference Approval...

Страница 19: ...or deactivation command over the bus Technical characteristics Power supply voltage 24 Vdc 5 Absorption min 5 5 mA max 20 mA Sensor range 5 C to 30 C Positioning In flush mounted boxes compatible wit...

Страница 20: ...is selected by changing the position of the first of the dip switches underneath the front panel lever this off at the sides to remove it alongside the diverter slider In both modes the temperature r...

Страница 21: ...iving International BTICINO Light BTICINO Light Tech SILVER LIGHT TECH finish front panel and knob optional Note for the installer with Living International Light and Light Tech BTICINO series entranc...

Страница 22: ...ed c Analysis interval it is possible to indicate the time interval between one temperature setpoint check and the next After checking the thermostat sends the temperature reading over the network in...

Страница 23: ...le length 25 m Protection against reverse polarity Indications 1 bus status indicator LED when flashing indicates data transmission via bus when lit steadily indicates lack of power supply negative or...

Страница 24: ...Output 1 Common NC1 Output 1 NC contact NO2 Output 2 NO contact C2 Output 2 Common NC2 Output 2 NC contact NO3 Output 3 NO contact C3 Output 3 Common NC3 Output 3 NC contact NO4 Output 4 NO contact C4...

Страница 25: ...230 Vac resistive 6A cosj 1 Max input cable length 25 m Protection against reverse polarity Indications 1 bus status indicator LED when flashing indicates data transmission via bus when lit steadily...

Страница 26: ...ontact O3 Output 3 NO contact O4 Output 4 NO contact C1 Output common 1 2 3 4 O5 Output 5 NO contact O6 Output 6 NO contact O7 Output 7 NO contact O8 Output 8 NO contact C2 Output common 5 6 7 8 V 24...

Страница 27: ...length 25 m Protection against reverse polarity Indications 1 bus status indicator LED when flashing indicates data transmission via bus when lit steadily indicates lack of power supply negative or i...

Страница 28: ...C6 Output 6 Common I8 Input 8 C2 Output 2 Common NC6 Output 6 NC contact I7 Input 7 NC2 Output 2 NC contact NO7 Output 7 NO contact I6 Input 6 NO3 Output 3 NO contact C7 Output 7 Common I5 Input 5 C3...

Страница 29: ...30 mA Inputs 2 analogue 0 10 V Maximum input cable length 5 m Outputs 2 analogue 0 10 V with max current 100 mA Protection against reverse polarity Indications 1 bus status indicator LED when flashing...

Страница 30: ...10 V V GND 10 10 Vdc support at input 1 OA1 Output 1 0 10 V V Output 1 support negative OA2 Output 2 0 10 V V Output 2 support negative N B The module must be programmed via the BUS line using the Sim...

Страница 31: ...djusts the brightness The dimmer can also be set with the Presence detection function This uses a motion sensor connected to the input of a digital module to increase the brightness of the light if th...

Страница 32: ...nction BUS power supply negative 24VDC BUS power supply Common for digital input I1 D BUS data line I1 24V digital input IA1 V For future uses N Dimmable output terminals L N Input voltage 240 10 VAC...

Страница 33: ...on and indicate any downtime caused by the disconnection of the outputs It is also possible to set an instant disconnection setpoint on the module when this is exceeded the module will deactivate all...

Страница 34: ...nals removable Positioning On DIN rail or in junction boxes Approvals CE Operating temperature 0 to 50 C Storage temperature 10 to 70 C Relative air humidity 5 to 95 with no condensation Accessories i...

Страница 35: ...mpleHome bus terminal board CONNECTION TERMINALS 1 BUS power supply negative 2 BUS power supply 24 Vdc 3 D BUS data line Technical characteristics Power supply voltage 24 Vdc 5 Absorption 20 mA Serial...

Страница 36: ...ts a data package containing the recorded temperature value via the bus The temperature sensor depending on the setpoint is updated and transmits a remote output activation or deactivation command via...

Страница 37: ...37 Fastening Unfastening Sensor mounting...

Страница 38: ...mA Indications 1 LEDs red indicating relay active 1 LED yellow indicating bus status when flashing indicates data transmission over the bus when lit steadily indicates lack of power supply negative or...

Страница 39: ...dications 1 LEDs red indicating relay active 1 LED yellow indicating bus status flashing indicates data transmission over the bus lit steadily indicates lack of power supply negative or incorrect conn...

Страница 40: ...rption MAX 30 mA Outputs 2 10A N O relay outputs 230 Vac resistive loads Indications 2 LEDs red indicating relay active Positioning On DIN rail or in flush mounted boxes Approvals CE Operating tempera...

Страница 41: ...nputs 3 pulse type Indications 1 bus status indicator LED yellow when flashing indicates data transmission via bus when lit steadily indicates lack of power supply negative or incorrect device connect...

Страница 42: ...ome automation system configuration Power supply 12 Vdc 24 Vdc Current absorption 355 mA 13 8 Vdc 175 mA 25 Vdc Size HxWxD 85 x 123 x 28 6 mm O C outputs YES 500 mA MAX Relay output 30 Vdc 5 A 250 Vac...

Страница 43: ...43 150 cm 120 cm Minitouch timer thermostat mounting...

Страница 44: ...ot used 3 CV5 Jumper for video closure 4 JP10 DO NOT ADJUST 5 CV6 DO NOT REMOVE 6 CV8 Termination 485 12 3 11 10 9 8 7 6 5 4 1 2 1 Touch screen 2 Key sensor 3 Door lock key 4 Privacy Doctor key progra...

Страница 45: ...2 3 4 5 1 140 145 cm 115 125 cm ALTO UP HAUT OBEN 14 5 cm 14 5 cm 1 2 2 3 140 145 cm 115 125 cm ALTO UP HAUT OBEN m 14 5 cm 2 1 1 2 2 3 140 145 cm 115 125 cm 2 3 4 5 1 140 145 cm 115 125 cm ALTO UP H...

Страница 46: ...5 touch screen 3 Tamper 4 Ethernet connector for future use 5 Terminal block for connection 6 Magic light Technical characteristics Colour Black Magic Light RGB LED illumination Display 3 5 7 cm colou...

Страница 47: ...47 Minitouch mounting 150 cm 120 cm...

Страница 48: ...nagement must take place via the WEB interface Technical characteristics The Serial Bridge is a Web Server device which by means of a PC browser tablet smartphone etc is able to do the following witho...

Страница 49: ...32 2 Alarm control unit TX RS232 12 12 Alarm serial port power supply terminals 485 A L B L Alarm supervisor connection terminals 2 LED indicating data transmission over home automation BUS 3 LED indi...

Страница 50: ...which include procedures to be sent to the SimpleHome automation system and or the S Series or VEDO security system The Serial Bridge is a Web Server device which by means of a PC browser tablet smart...

Страница 51: ...et port LED 1 lit connection active LED 2 flashing data transfer in progress 8 LED indicating data transmission to alarm control units 9 Reset button 10 Dip switches 1 2 3 For future uses 4 485 termin...

Страница 52: ...on the DALI or DMX communication BUS Commands sent to DMX power supply units can switch the connected light source on off dim it or adjust its colour if using RGB lights Commands sent to the DALI int...

Страница 53: ...ules CONNECTION TERMINALS Terminal Function BUS power supply negative BUS power supply 24 Vdc D BUS data line DA DA DALI BUS A L B L GND DMX BUS Jumper J1 DALI DMX function selector SIMPLEPROG THE COM...

Страница 54: ...CERTIFIED MANAGEMENT SYSTEMS w w w c o m e l i t g r o u p c o m Via Don Arrigoni 5 24020 Rovetta BG Italy 8 ed 1rev 07 2020 cod 2G40001125...

Отзывы: