Parameter Programming 

6

 Some parameters  

are accessible only 
when the respective  
functionality is installed. 
(see 

'

Specifications

'

).

 

 
 
 

 

 

 

 

-  Changing  

Point Position 

value

  

reflects on the real value 
of all parameters 
with ISU! 

E.g.: changing  

Point Position 

value 

from (0) to (0.0) 
would change 
a set-point value 
of 100 to 10.0!!! 

 

Device parameters 

 

TI08 is a programmable device whose  
service behavior is determined by a set  
of parameters. All the parameters, along  
with their names, symbols, and value ranges,
are given in Table 1.

 

Setting numerical parameter value 

 

Enter parameter value adjustment mode 
(see '

Program Levels

').

 

 

The whole part of the value together with 
the left zeroes appears on the display,  
and the rightmost digit blinks.

 

 

To select another digit, press 

 

.

 

 

The 3 rightmost digits can accept values 
from 

0

 to

 

9

, and the leftmost digit 

can also accept the values 

-

 and

 

`

.

 

 

To increase or decrease the blinking digit 
value, use respectively 

 or 

 

.

 

 

Confirm the adjusted value by pressing 
simultaneously

 

 + 

 

or 

 + 

.

 

 

If the new value has not been confirmed  
and no key has been pressed for a certain 
period of time, value adjustment 
automatically ceases, and the parameter 
retains its initial value.

 

Setting symbolic parameter value 

 

Enter parameter value adjustment mode 
(see '

Program Levels

').

 

 

Read the blinking parameter value. 

 

To change the value, use 

 or 

,  

and to confirm, press 

 + 

  

or 

 + 

.

 

 

If the new value has not been confirmed  
and no key has been pressed for a certain 
period of time, value adjustment  
automatically ceases, and the parameter 
retains its initial value.

 

 

Содержание TI08

Страница 1: ...el 359 32 646523 646524 fax 634089 e mail info comeco org WWW COMECOGROUP COM TI08 OPERATION MANUAL Please read this Operation Manual before mounting and operating Save the Manual for future references PROCESS INDICATOR TRIP ALARM UNIT v5 1 05 14 ...

Страница 2: ...low through the RC circuit All signal wires must be shielded They must not be packaged together with power cables Never lay the signal wires close to inductive or capacitive noise sources such as relays contactors motors etc All shields have to be grounded ONLY at one end as closer as possible to the indicator terminals Avoid sharing supply lines with powerful consumers especially with inductive l...

Страница 3: ...10 mA see Specifications Input signal wiring Connect the input with regard to its type through the respective and depending on the case type see Specifications terminals on the device back Voltage transmitters should be powered ONLY by external source Output wiring Connect the outputs with regard to their types see Specifications via the respective terminals Power supply wiring Connect the right p...

Страница 4: ...1 e1 Relay switching differential over set point for output OUT1 Differential 1 me1 Relay switching differential under set point for output OUT1 Time On 1 ym1 ON duration of pulsed output OUT1 Time Off 1 y 1 OFF duration of pulsed output OUT1 Hold On 1 km1 Holds the output OUT1 reaction when being activated Hold Off 1 k 1 Holds the output OUT1 reaction when being deactivated The same 7 parameters ...

Страница 5: ...n safe limits preserving them from random changes cooL hEAt cooling activates over set point heating activates under set point 0 9999 ISU less than high range limit Set Point 1 0 9999 ISU less than Set Point 1 low range limit 0 9999 sec pulse duration value 0 disables pulse mode 0 9999 sec pause duration value 0 disables pulse mode 0 9999 sec Value 0 disables hold mode 1999 9999 ISU within operati...

Страница 6: ... appears on the display and the rightmost digit blinks To select another digit press The 3 rightmost digits can accept values from 0 to 9 and the leftmost digit can also accept the values and To increase or decrease the blinking digit value use respectively or Confirm the adjusted value by pressing simultaneously or If the new value has not been confirmed and no key has been pressed for a certain ...

Страница 7: ...rameter If the whole part of PV cannot be entirely displayed the unit generates a blinking overflow message oL or oL depending on PV sign If PV is out of the device physical operating range it displays blinking symbolic message __ under range or over range Upon entering Basic level TI08 may display the init message indicating that some time is necessary for filter initialization The noiS message m...

Страница 8: ...n pressed for a while the device automatically returns to Basic level storing all confirmed changes For quick exiting and saving use key combination or Output Control Alarm output operation The alarm outputs operate according to the control algorithm parameters When an error is detected see Error messaging the outputs deactivate and restore after all discrepancies have been resolved and programmin...

Страница 9: ... h ER11 ER21 ym1 ym2 out of range ER12 ER22 y 1 y 2 out of range ER13 ER23 km1 km2 out of range ER14 ER24 k 1 k 2 out of range ER15 ER25 e1 e2 out of range ER16 ER26 me1 me2 out of range ER17 ER27 1 2 outside L h ER18 ER28 x mex under input range ER19 ER29 x ex over input range device physical operating range considering Input Correction In some cases TI08 finds discrepancies in parameter values t...

Страница 10: ...a normal signal It is possible only if the input signal has not been changed with more than the Gradient value for 4 subsequent samples If the device has not determined a normal signal for 20 subsequent samples noiS appears on the display see Basic level Low pass filter This first order filter acts ONLY within a certain band around filter output value This has been designed to cut periodic noises ...

Страница 11: ...326 1 and meets the requirements of Directives 2004 108 EC and 2006 95 EC Krasimir Darakchiev CEO COMECO Inc Waste Disposal Do not dispose of electronic devices together with household waste material If disposed of within European Union this product should be treated and recycled in accordance with the laws of your jurisdiction implementing Directive 2012 19 EU on waste electrical and electronic e...

Страница 12: ...g IP65 IP54 IP44 IP20 Warranty and Support article number serial number manufacturing date QC check mark passed stamp 88 Slavyanska Str P O Box 378 Plovdiv 4000 BULGARIA tel 359 32 646523 646524 fax 359 32 634089 646517 e mail support comeco org QD 8 2 4 WC Warranty COMECO warrants this product to be free from defects in materials and workmanship for 2 years If your unit is found to be defective w...

Отзывы: