The following parameters are to be programmed:
8.6.1.1. Alarm limit
parameter
AlL
PARAMETER
MIN.
MAX.
UNIT
DEFAULT
AlL
`999
9999
depending on the selected input in
inP
0000
8.6.1.2. Hysteresis
parameter
hYSt
PARAMETER
MIN.
MAX.
UNIT
DEFAULT
hYSt
0000
9999
depending on the selected input in
inP
0000
8.6.1.3. Hold time
parameter
hoLd
PARAMETER
MIN.
MAX.
UNIT
DEFAULT
hoLd
0)0
1@0
seconds
0)0
This parameter is assigned to hold the alarm reaction for certain period of time for eliminating undesirable
switches of the alarm output.
8.6.1.4. Relay connected to alarm output
parameter
outP
VALUE
COMMENT
nonE
No relay is assined to alarm output (only front-panel LED is used)
rEL1
-
rEL8
Relay number
Only the actually mounted relays are available.
Relay K9, if installed, cannot be assigned to an alarm output, but is used to signal system failure.
Be aware that it might be activated not only by the alarm, but also because of some other failure.
8.6.2.
Low limit alarm type
When the parameter
tYPE
value is
+7__
, the parameter tree becomes the same as that for
the upper limit type alarm. The parameters have the same meaning. The only difference is in the static
correspondence between alarm input and alarm state (Fig. 8.5).
Fig. 8.5