C. RESETTING THE FLAME SAFETY CONTROL
The Reflect-O-Ray burner system is equipped with an
automatic lockout control, which is activated after 30
seconds if a burner should fail to ignite. If your burner
should lock out, it should be reset by the follow method:
1. Turn off the toggle switch at the burner or turn down
the thermostat to stop the exhauster.
2. Wait five minutes for the ignition timer switch to cool
and automatically reset.
3. Turn the power back on, either by turning the toggle
switch back on or turning the thermostat back up. The
burner should ignite and all three indicator lights should
come on.
4. The system will now automatically recycle on the
thermostat to maintain desired room temperature.
IF THE BURNER WILL NOT LIGHT AFTER TWO
RESET TRIALS, CONTACT YOUR INSTALLER FOR
SERVICE.
D.
STOPPING THE SYSTEM FOR SERVICE
1. For servicing an individual burner or exhauster, turn off
the service toggle switch, which should be mounted
within two feet of the unit. Close the gas supply to
burners, at the individual burner gas cocks'.
2.
To service the thermostat, turn off the electrical power
at the main power disconnect box.
3.
Before servicing any gas component; shut off the gas
supply at the meter by closing the main gas valve.
BURNER INDICATOR LIGHTS
1. DEAD MODE: The burner power supply has been
interrupted. (Trouble shooting checks: Thermostat
setting, circuit breaker/fuse, power disconnect switch,
loose wires)
2. START-UP MODE: When the thermostat closes,
power light energizes, airflow light energizes and
burner light energizes after flame is proven.
3. NORMAL OPERATING MODE: All three lights are on.
The burner will continue to fire in the normal mode until
the thermostat is satisfied.
4. AIRFLOW INTERRUPT MODE: There is electrical
power to the burner, however the air flow switch has
not closed. (Trouble shooting checks: Vacuum
exhauster is not running, there is an obstruction in the
inlet or outlet of the system, airflow switch is defective.
5. LOCKOUT MODE: After attempting to ignite for a
maximum of 30 seconds, the burner ignition circuit will
shut down or lockout. Reset as described above in
"C".
Page 35