background image

 

Omega II

®

 Installation, Operation & Maintenance 

 

 

Page 32 

Combustion Research Corporation 

   

WARNING 

FIRE OR EXPLOSION HAZARD 

 
 

 

 

IMPROPER INSTALLATION, ADJUSTMENT, 
ALTERATION, SERVICE OR MAINTENANCE 
CAN CAUSE DEATH, SEVERE INJURY 
AND/OR PROPERTY DAMAGE.

 

1. Flame is lit automatically.  Do not light the flame 
manually.  
2. Before lighting burner flame, smell around the 
appliance for gas.  Be sure to smell next to floor 
because LP gas is heavier than air. 
3. IF YOU SMELL GAS:

 

  Turn off the gas supply at the appliance service 

valve.  On LP gas systems, turn off gas supply at 
the gas tank. 

  Do not light any appliances in the house. 

  Do not touch electrical switches or use the phone. 

  Leave the building and use a neighbor's phone to 

call your gas supplier. 

  If you cannot reach your gas supplier, call the fire 

department

4. Do not force the gas control knob.  Use only your 
hand to push down or turn the gas control knob.  
Never use any tools.  If the gas control knob will not 
operate by hand, a qualified service technician should 
replace the gas control.  Force or attempted repair 
may result in a fire or explosion. 

5. The gas control must be replaced in case of any 
physical damage, tampering, bent terminals, missing 
or broken parts, stripped threads, and evidence of 
exposure to heat. 

 

MAINTENANCE 

Regular preventive maintenance is important in applications 
that place a heavy load on system controls, such as in the 
commercial cooking and agricultural and industrial 
industries because: 

1.  In applications where the equipment operates 100,000- 

200,000 cycles per year.  Such heavy cycling can wear 
out the gas control in one to two years. 

2.  Exposure to water, dirt, chemicals and heat can damage 

the gas control and shut down the control system. 

 

NOTICE 

Do not apply a jumper across or short the valve coil 
terminals.  Doing so may damage the ignition module. 

 

 

 

 

   

WARNING 

FIRE OR EXPLOSION HAZARD 

 
 

 

 

IMPROPER INSTALLATION, ADJUSTMENT, 
ALTERATION, SERVICE OR MAINTENANCE 
CAN CAUSE DEATH, SEVERE INJURY 
AND/OR PROPERTY DAMAGE.

 

Do not disassemble the gas control.  The gas control 
contains no replaceable components.  Attempted 
disassembly or repair may damage the gas control. 

The maintenance program

 should include regular 

checkout of the gas control. Maintenance frequency must 
be determined individually for each application.  Some 
considerations are: 

1.  

Cycling frequency.

  Appliances that may cycle 100,000 

times annually should be checked monthly. 

2. 

 Intermittent use.

  Appliances that are used seasonally 

should be checked before shutdown and again before the 
next use. 

3.  

Consequence of unexpected shutdown.

  Where the 

cost of an unexpected shutdown would be high, the system 
should be checked more often. 

4.  

Dusty, wet or corrosive environment. 

 Since these 

environments can cause the gas control to deteriorate more 
rapidly, the system should be checked more often. 

The gas control should be replaced if

:

 

1.  It does not perform properly on checkout or trouble-

shooting. 

2.  The gas control knob is hard to turn or push down, or it 

fails to pop back up when released. 

3.  The gas control is likely to have operated for more than 

200,000 cycles. 

 

CHECKOUT PROCEDURE 

Before leaving installation, several complete operating 
cycles should be observed to see that all components are 
functioning properly. 

1.  Before turning on the main electrical power switch, be 

sure all gas supply lines are purged of air. 

2.  Close main manual shutoff valve and wait for 5 minutes, 

then turn "A" valve to counter clockwise 

 to "ON" 

position. 
CAUTION:  Check for positive gas seal using soap 
solution on valve inlet and all upstream pipe 
connections. 

3.  Turn on main electrical power switch and close 

thermostat contacts. 

4.  After the control is powered it will automatically energize 

the spark and the gas valve. 

 
 

!

Содержание Omega II

Страница 1: ...r birth defects or other reproductive harm Contact factory for further information Installer Please take time to read and understand these instructions prior to any installation Installer must give a...

Страница 2: ...wheel can cause severe injury Do not operate the vacuum exhauster without impeller Loose clothing can be drawn into unguarded inlet and entangle with impeller wheel Keep hands and fingers away from in...

Страница 3: ...lation 13 Technical Data 14 System Dimensions 15 Clearance To Combustibles 16 17 Side Shield Installation 18 Combustion Air 19 20 Venting 22 24 Electrical Information 25 Thermostat Wiring 27 System St...

Страница 4: ...Omega II Installation Operation Service Combustion Research Corporation This Page Intentionally Left Blank...

Страница 5: ...e sharp edges The use of gloves will also help in reducing the transfer of dirt and oils to the surface of the reflectors If additional Installation Operation and Service Manuals are needed contact yo...

Страница 6: ...ration Maintenance Page 2 Combustion Research Corporation Operating Instructions Label P N 900 2701 Rating Plate Label P N 900 2601 Clearance to Combustibles Label P N 900 2730 Side Panel Side Panel V...

Страница 7: ...CODES In the absence of local codes the installation must conform to the latest edition of United States National Fuel Gas Code ANSI Z223 1 NFPA 54 Canada CAN CGA B149 1 and 2 Canadian Electrical Cod...

Страница 8: ...as to maintain the required clearance to combustibles A temporary sample sign can be found at the end of the manual GENERAL CONSIDERATIONS Combustion Research Corporation Factory Representatives are e...

Страница 9: ...Next secure joints with the self drilling and taping screws provided use three per joint Clean off excess sealer with a damp cloth 4 Next install hangers supports by sliding them into place and positi...

Страница 10: ...5 55 118 S 55 55 118 S 55 55 118 S 118 S 118 S 118 S 55 55 118 S 118 S 118 S 118 S 10 SYSTEM 20 SYSTEM 30 SYSTEM 40 SYSTEM 50 SYSTEM 55 55 118 S 118 S 40 SYSTEM 55 55 118 S 118 S 30 SYSTEM 118 S 55 55...

Страница 11: ...TUBE SYSTEM 4 0 U TUBE SYSTEM 44 66 5 U 10 TUBE LENGTH 10 U 20 TUBE LENGTH 66 15 U 30 TUBE LENGTH 66 66 66 25 U 50 TUBE LENGTH 66 66 66 66 66 20 U 40 TUBE LENGTH Note Install Reflector inside hanger...

Страница 12: ...sh a chain with a minimum 90 lb workload trade size 3 or larger A minimum of 12 30 cm of hanging chain is recommended This allows for system expansion and contraction reducing the likelihood of reflec...

Страница 13: ...e The combination hanger is designed so that the reflector angle will be horizontal when suspended from the top loop or at a 30 angle when suspended from the offset loop see the illustration below The...

Страница 14: ...od shall be attached and suspend the reflector hangers at intervals of eight to ten feet 8 10 At least one vertical threaded rod shall be placed at every elbow and or tee connection The threaded rod i...

Страница 15: ...tal screws 2 Connect the thermostat gas and electrical supplies and hook up the exhaust flue and combustion air supply as it outlined in this manual 3 The system is now ready to be fired Refer to the...

Страница 16: ...ream side of the regulator will damage the control valve in the gas train The outlet pressure of the service regulators should be set at 7 W C for natural gas and 11 W C for LP gases propane gases If...

Страница 17: ...hese instructions can result in property damage Check the pipe and tubing ends for leaks before placing heating equipment into service When checking for gas leaks use a soap and water solution never u...

Страница 18: ...st be measured with a water or red oil manometer NOT A DIAL GAUGE All measurements must be made when this heater and all other gas burning equipment connected to the gas supply system are operating at...

Страница 19: ...9 11 24 9 29 10 39 4 49 1 31 2 41 1 51 2 0928 NG LP 115 000 14 8 19 11 24 9 29 10 39 4 49 1 31 2 41 1 51 2 0929 NG LP 120 000 19 11 24 9 29 9 39 4 49 1 58 11 41 1 51 2 61 7 0930 NG LP 125 000 19 11 24...

Страница 20: ...ounted lower than 9 from the floor unless fitted with protective screens The following illustrations and information give minimum acceptable clearance to combustibles Minimum clearances to combustible...

Страница 21: ...38 48 44 54 0941 0945 NG LP 180k to 200k 7 80 90 48 58 24 38 48 44 54 A C C B1 HORIZONTAL MOUNTING 30 DEGREE ANGLE MOUNTING 20 FEET DOWN STREAM FROM BURNER A B1 C C A B2 D C A B2 D D A C B1 E A C B1...

Страница 22: ...imately one every two feet The side shield expansion joint must match the reflector expansion joint DO NOT SCREW THE EXPANSION JOINTS TOGETHER Reflector Tube and reflector hanger Reflector intermediat...

Страница 23: ...DE AIR SUPPLY RECOMMENDED 1 The outside air intake assembly PN 0314 00 consists of 1 4 OD inlet hood I 4 OD 24 long inlet flex and 2 clamps 2 The assembly may be extended by adding up to 20 of the app...

Страница 24: ...f six feet 6 between the exhaust port and the fresh air intake Maintain a minimum of six inches 6 between the inlet hood and the exterior wall Install 4 diameter flex nearest inlet trunk Do not instal...

Страница 25: ...ch O D flue pipe is recommended Maximum flue length may be twenty feet 20 Do not use more than two 2 90 elbows Insulate as required to prevent condensation 2 Use B vent for any roof penetration Any ve...

Страница 26: ...control all associated heaters 4 Connections to a common stack should be staggered so as to avoid direct opposition between streams of combustion gasses 5 A 1 minimum clearance must be maintained arou...

Страница 27: ...BUSTIBLE WALLS HORIZONTAL VENTING COMBUSTIBLE WALLS 18 4 Type B Vent pipe 4 ingle wall vent pipe Omega II Exhaust Vent Cap PN 1811 VT 400 Wall thimble Min 6 Max 18 4 Single wall vent pipe Seal penetra...

Страница 28: ...gs This air displacement should be done mechanically and interlocked with the burners This will insure that both the heaters and the ventilation operate simultaneously DO NOT USE UNVENTED SYSTEMS IN A...

Страница 29: ...ly line DO NOT RUN THE ELECTRICAL SUPPLY LINES DIRECTLY ABOVE THE REFLECTOR OR BELOW THE REFLECTOR CLEARANCE TO COMBUSTIBLES MUST BE MAINTAINED NOTE If any of the original wire as supplied with the ap...

Страница 30: ...ation Operation Maintenance Page 26 Combustion Research Corporation INTERNAL WIRING DIAGRAMS WARNING DO NOT ATTEMPT TO RE WIRE INTERNAL BURNER WIRING 24 VOLT TRANSFORMER IS NOT TO BE USED FOR ANY THER...

Страница 31: ...IRING LOW VOLTAGE THERMOSTAT WIRING White Black Black L1 H 115V 60Hz COIL COIL 6 3 4 1 5 2 Brown L2 N T R C W G Y Low voltage thermostat PN 5483 00 TOP VIEW NOTE Brown lead is not used Cap off with wi...

Страница 32: ...mine if the motor is operating at safe load conditions and not overloaded RADIANT TUBING CHECK 1 Inspect entire network of radiant tubing to insure that all fittings are securely screwed together 2 In...

Страница 33: ...ns off the spark ignition 6 After the thermostat is satisfied the power is removed from the burner assembly causing the ignition control and gas valve to turn off and the blower shuts down 7 System wa...

Страница 34: ...as chains for wear If any wear is present the system must not be operated until the chain s or associated hardware has been replaced Look for any deterioration in the housing assembly Replace or repa...

Страница 35: ...y disarm the system 5 In order to initiate a re ignition trial the power must be interrupted for 5 minutes POWER INTERRUPTION ON START 1 No gas will flow during power interruption 2 Normal sequence wi...

Страница 36: ...the valve coil terminals Doing so may damage the ignition module WARNING FIRE OR EXPLOSION HAZARD IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE DEATH SEVERE INJURY AND O...

Страница 37: ...he thermostat or controller above room temperature to call for heat 3 Watch for ignition spark immediately or following pre purge See ignition module specifications 4 Time length of ignition operation...

Страница 38: ...of transformer NO Is there 24 volt power at the ignition control Is there 24 volts to the pressure switch NO Replace blower assembly NO Is blower obstructed YES Remove obstruction and realign blower w...

Страница 39: ...pressure at the manifold pressure tap NG 3 5 LP 10 0 Check gas orifice for blockage proper size YES Replace gas valve NO Adjust supply gas pressure to proper levels see name plate YES Repair or repla...

Страница 40: ...Omega II Installation Operation Maintenance Page 36 Combustion Research Corporation...

Страница 41: ...or all systems except for 0941 thru 0945 systems Mixing Nozzle For 0941 0945 systems Gas Valve Specify Manufacture Manufacture Model No Gas Orifice Specify Input Gas Inspection Window Combustion Spinn...

Страница 42: ...diameter mushroom style round vent For single wall or B Vent Wt 0 75 lbs 1811 VT 400 ROOF OR WALL VENT 4 diameter High Wind mushroom style round vent For B vent Wt 0 5 lbs 1811 VT 600 ROOF OR WALL VEN...

Страница 43: ...aluminized steel heat treated radiant tube 9 9 long Wt 12 75 lbs 0360 00 STANDARD REFLECTOR Aluminum 10 long Wt 5 0 lbs 0361 00 COMBINATION HANGER Heat tube standard reflector hanger for 3 5 tube plat...

Страница 44: ...ector for 3 5 tube plated 1 4 dia wire Wt 0 75 lb 0465 00 DEEP DISH REFLECTOR SUPPORT Intermediate support for deep dish reflector for 4 0 tube plated 1 4 dia wire Wt 0 75 lb 0366 00 0367 00 SIDE SHIE...

Страница 45: ...NT SHALL CRC BE LIABLE FOR SPECIAL INDIRECT CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY TYPE OR DESCRIPTION WHETHER ARISING UNDER CONTRACT WARRANTY TORT NEGLIGENCE STRICT LIABILITY OR ANY OTHER THEORY...

Страница 46: ...ate courts maintaining jurisdiction over all controversies in the State of Michigan VOIDING OF WARRANTIES Each of the following listed events conditions acts or omissions by any person or entity may v...

Страница 47: ...must provide signs that specify the maximum stacking height so as to maintain the required clearance to combustibles The following is a temporary sign that can be used until a permanent label is obtai...

Страница 48: ......

Страница 49: ......

Страница 50: ...COMBUSTION RESEARCH CORPORATION 2516 Leach Road Rochester Hills Michigan 48309 3555 Telephone No 248 852 3611 www combustionresearch com...

Отзывы: