Calculating vent system length
To calculate the length of the system you need, deduct the equivalent feet for each vent piece used in the system
from the recommended maximum duct run.
Duct Run Calculation
Recommended maximum run
8” or 3-1/4 x 10” duct
50 ft
Vent piece deduction
Each 90º elbow used
9 ft
Each 45º elbow used
5 ft
Each 7” to 3/14 x 10” transition used
7 ft
Side wall cap with damper
0 ft
Roof cap
0 ft
Duct Run Calculation example:
One roof cap, two 90º elbow, and one 45º elbow used:
0ft + 9ft + 9ft + 5ft = 23ft used.
Deduct 23ft from 50ft, 27ft maximum available for straight duct run.
Venting methods
•
This range hood is factory set for venting
through the roof or wall.
•
Vent work can terminate either through
the roof or wall. To vent through a wall, a
90° elbow is needed.
IMPORTANT:
•
NEVER exhaust air or terminate duct
work into spaces between walls, crawl
spaces, ceiling, attics or garages.
All exhaust must be ducted to the
outside.
•
Use metal/aluminum duct work only.
•
Fasten all connections with sheet metal
screws and tape all joints with certified
Silver Tape or Duct Tape.
•
Use caulking to seal exterior wall or roof
opening around the cap.
Содержание 7227.0005
Страница 6: ...6 www combisteel com INSTALLATION Tools needed Parts supplied...
Страница 18: ...18 www combisteel com Hood mounting Bracket Circuit Diagram...
Страница 27: ...27 www combisteel com INSTALLATIE Benodigd gereedschap Meegeleverde onderdelen...
Страница 39: ...39 www combisteel com Montagebeugel afzuigkap Circuit diagram...
Страница 48: ...48 www combisteel com INSTALLATION Ben tigte Werkzeuge Gelieferte Teile...
Страница 60: ...60 www combisteel com Haubenbefestigungshalterung Schaltkreisdiagramm...
Страница 69: ...69 www combisteel com INSTALLATION Outils n cessaires Pi ces fournies...
Страница 81: ...81 www combisteel com Support de capot Diagramme de circuit...
Страница 88: ...88 www combisteel com...