The MPR has a normally closed N/C alarm contact (rated  5 A  250 V resistive load). It will be possible to give an 
external alarm signal. This contact is signed with X1 and X2 (ALARM) in the base of the regulator. 
When alarm condition disappears, the regulator will reset itself automatically. 
 
 

••••

 

No Supply voltage alarm 
When the voltage supply is lost, the digital display is off and the alarm contact (X1 and X2) is closed. 

••••

 

Low PF value in the network 
If after 15 minutes the preset PF is not achieved, the alarm contact closes and the actual PF is displayed. 
At  the  same  time  the  CosØ  Led  flashes.  The  contact  closes  again  when  the  preset  conditions  are  met. 
The CosØ led however continues to flash until the RESET PROCEDURE is performed. 

••••

 

Voltage alarm  
When  the  supply  voltage  is higher than 110%  of the rated value (for at least 10 secs.), the regulator will 
switch off, step by step, all capacitors banks. Under such condition the MPR displays the VOLTAGE value, 
the related VOLT led (V) flash and  the N/C  alarm contact  for  the external signal     ( X1 - X2 ) will close. 
The alarm condition will clear  when the voltage is  again within correct parameters. The "V" Led however 
will  continue to flash in order to show, to  the operator, which alarm condition was on. To reset the alarm 
memory the RESET PROCEDURE should be performed.  
WHEN  THE  VOLTAGE  ALARM  CONDITION  IS  ON,  ALL  MANUAL  AND  AUTOMATIC  OPERATING 
FUNCTIONS ARE UNAVAILABLE. 

••••

 

Current signal alarms  

  Max  current.  It  occurs  when  the  current  value  in  the  secondary  of  the  CT  transformer  is  higher  than 

5Amps  (for  at  least  10  secs).  In  such  a  condition,  the  MPR  displays  the  CURRENT  value,  the  related 
CURRENT  Led  (A)  will  flash  and  the  N/C  alarm  contact  (  X1  -  X2  )  will  close.  The  alarm  fault  condition 
clears  when the current returns  to rated conditions. The "A" led however will continue to flash in order to 
show,  to  the  operator,  which  alarm  condition  was  on.  To  reset  the  alarm  memory  the  RESET 
PROCEDURE should be performed. 

  Min  current  alarm.  It  occurs  when  the  current  value  in  the  secondary  side  of  the  CT  transformer  is 

lower than 500 mAmps (for at least 10 secs). In such a condition, the MPR displays the CURRENT value 
will flash. When the Min current alarm is operating, the MPR is only able to switch off the capacitor banks 
if  the  PF  value  is  more  than  1.  The  alarm  fault  condition  clears  when  the  current  returns  to  rated 
conditions. 

 Current lower than 10 mAmps. In this condition the regulator will only operate in MANUAL mode. The 

numerical display will show the symbols"-.--", and the related CURRENT Led (A) will flash. The N/C alarm 
contact ( X1 - X2 ) will close. The alarm fault condition clears when the current returns to rated conditions. 
The "A" Led however will continue to flash in order to show, to the operator, which alarm condition was on. 
To reset the alarm memory the RESET PROCEDURE should be performed. 

••••

 

Temperature alarm (only for MPR8) 
The  MPR8  regulator  incorporates  a  temperature  control  circuit.  The  temperature  sensor  must  be 
connected with the regulator switched off. 

 First step (35°C).   Causes the N/O contact (5 A 250 V resistive load) connected to terminal P1 and P2 

(VENT)  to  close.  The  temperature  differential  is  5  °C.  This  contact  should  be  used  to  control  the  pane l 
ventilation fans.  

 Second step (50°C )  The regulator will rapidly switch off all capacitors banks. With this alarm condition, 

the MPR displays the TEMPERATURE value, the related TEMPERATURE Led (°C) will flash and the N/C 
alarm  contact  for  the  external  signal  (  X1  -  X2  )  will  close.  The  alarm  fault  condition  clears  when  the 
temperature  value  falls  below  45  °C.  The  "C"  Led  ho wever  will  continue  to  flash  in  order  to  show  which 
alarm condition was on. To reset the alarm memory state the RESET PROCEDURE should be performed. 
 
WITH  THE  MAXIMUM  TEMPERATURE  ALARM  CONDITION  ON,  ALL  MANUAL  AND  AUTOMATIC 
OPERATING FUNCTION ARE HALTED 

 

••••

 

Supply interrupts 
To  avoid  dangerous  operating  condition  on  contactors  when  the  supply  voltage  is  interrupted,  the  MPR 
switches  off  all  capacitors  banks  until  reconnection.  Micro  breaks  trouble  on  network  must  be  solved  by 
the client. 

 

RESET PROCEDURE 

 
It is necessary to select the values corresponding to the flashing Led (alarm memory state condition) and 

press the 

Prog.

button. 

 

8.  WORKING TROUBLES and SOLUTION 

Most malfunctions are caused by incorrect connections. The most common faults are as follow: 

Содержание MPR

Страница 1: ...I ISTRUZIONI REGOLATORE ELETTRONICO tipo MPR INSTRUCTION MANUAL ELECTRONIC POWER FACTOR REGULATOR type MPR MANUEL D INSTRUCTIONS REGULATEURS AUTOMATIQUES DE PUISSANCE REACTIVE type MPR MANUAL DE INSTRUCCIONES REGULADOR ELECTRÓNICO DE POTENCIA REACTIVA tipo MPR ITALIANO Prog C K PF cosΦ Φ Φ Φ V A _ Select 1 2 3 4 5 6 made in Italy MPR8 7 8 C Power Factor Regulator ...

Страница 2: ...ag 12 pag 13 pag 13 pag 14 pag 15 pag 15 pag 16 FRANÇAIS 1 PRESENTATIÓN 2 CHOIX du TRANSFORMATEUR D INTENSITE T I 3 INSTRUCTION D EMPLOI 3 1 CONNEXION ELÈCTRIQUES 3 2 FIXATION MECANIQUE 3 3 PUISSANCE des BATTERIES 3 4 NOMBRE des GRADIN POSSIBLES 4 FONCTIONNEMENT AUTOMATIQUE MANUEL 5 VISUALISATION 6 REGLAGE de BASE Régulation du C K Régulation du Facteur de Puissance 6 1 SAUVETAGE DES DONNES 7 ALAR...

Страница 3: ...mm 2 I corrente massima circolante sul secondario del TA 5A 0 08 resistenza interna del regolatore In presenza di carichi induttivi monofase sistema trifase squilibrato montare il T A sulla fase della rete con maggior necessità di rifasamento cosfì più basso e o maggior assorbimento di corrente elettrica I cavi del secondario del T A dovranno essere di sezione pari ad almeno 2 5 mm 2 Il collegamen...

Страница 4: ... appositi accessori forniti a corredo 3 3 POTENZA delle BATTERIE Il regolatore basa il proprio funzionamento sulla sequenza lineare l inserzione o la disinserzione delle batterie avviene quindi in successione numerica partendo dalla prima Per un corretto funzionamento dell impianto le batterie devono essere dimensionate in modo da risultare a ognuna uguale alla precedente esempio 1 1 1 1 1 1 b ogn...

Страница 5: ...alizzare in successione sul display i valori cosΦ Φ Φ Φ V A C cosΦ Φ Φ Φ V A C cosΦ Φ Φ Φ V A C cosΦ Φ Φ Φ V A C All accensione dello strumento la grandezza visualizzata sul display é il valore di COSFI istantaneo della rete 6 PROGRAMMAZIONI vanno eseguite dopo l allacciamento del regolatore in rete in base alla potenza della prima batteria di condensatori ed al grado di rifasamento medio che si d...

Страница 6: ...desiderato mediante l utilizzo del tasto decremento o incremento Si consiglia d impostare almeno il valore 0 95 induttivo Select PF _ I valori capacitivi di cosfì vengono indicati a display con il segno antecedente la misura es 95 N B Il regolatore viene pretarato in fabbrica a C K d 03 e Cosfì 0 97 con tale predisposizione trova la condizione di giusto rifasamento quando il Cosfì di linea rientra...

Страница 7: ...sinserzione delle batterie di condensatori in caso di sovracompensazione capacitiva mentre non pregiudica le funzioni manuali Al cessare della condizione anomala il regolatore riprende il normale funzionamento Corrente nulla Io una corrente circolante sul circuito amperometrico secondario del T A inferiore al valore 10mA causa l allarme di Corrente nulla Tale stato determina la visualizzazione del...

Страница 8: ...ficare il collegamento dello 0Vac sulle bobine dei teleruttori c Verificare il collegamento 220Vac sul morsetto C d Verificare il corretto funzionamento dei teleruttori Visualizzazione dicitura CAP sul display a Linea capacitiva nel punto di installazione del T A b T A sulla fase sbagliata collegare il TA sulla fase R v paragrafi 2 e 3 1 c Cosfì di linea inferiore ai valori 0 15 induttivo o 0 15 c...

Страница 9: ...uttore o disgiuntore posto in stretta vicinanza dell apparecchio facilmente raggiungibile da parte dell operatore e marcato come dispositivo d interruzione Quest apparecchio dovrà essere destinato solo all uso per il qual è stato espressamente concepito Ogni altro uso è da considerarsi improprio e quindi pericoloso Per un corretto funzionamento degli impianti non si dovranno mai superare i limiti ...

Страница 10: ...ace C T on the phase where Power Factor is lower and or where higher current value is absorbed The cables at the secondary of C T have to be of 2 5mm 2 section The C T connection must not to be protected with fuses or interrupted by switch The C T has to be connected to the line upstream the load and the P F Regulator the C T can then measure the current demanded by the load inductive and capaciti...

Страница 11: ...KS the regulator works according to binary logic sequence the switching on and off of capacitors banks always start from the first bank For correct operation of the automatic bank the power ratio per bank should be a equal to each other 1 1 1 1 1 1 1 1 b double of the previous bank 1 2 4 8 16 32 c equal or double of the previous bank 1 1 2 2 4 4 3 4 NUMBER of STEPS is determined by the power combi...

Страница 12: ...ill be switched off automatically When the power returns the regulator will again insert all banks step by step 5 DIGITAL DISPLAY It is possible to read the values of PF VOLTAGE CURRENT and TEMPERATURE C on the digital display T he current value should be multiplied by the CT ratio to determine the actual load current The TEMPERATURE reading is as measured at the point of external control by the s...

Страница 13: ... 0 2 0 2 3000 5 600 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 2 0 2 4000 5 800 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 2 5000 5 1000 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 When the CT secondary current signal is lower than 2 amps the C K value should be increased by 0 1 When using the regulator on 220 230 Vac networks the C K values should be doubled means installation of C T with primary value too small PF setting Af...

Страница 14: ...00 mAmps for at least 10 secs In such a condition the MPR displays the CURRENT value will flash When the Min current alarm is operating the MPR is only able to switch off the capacitor banks if the PF value is more than 1 The alarm fault condition clears when the current returns to rated conditions Current lower than 10 mAmps In this condition the regulator will only operate in MANUAL mode The num...

Страница 15: ...ctor functioning Displayed CAP on display a Possible capacitive load condition b CT installed in the wrong phase connect to phase L1 c P F lowers than 0 15 IND or CAP Displayed EEE on display Minimum current alarm or zero current signal Led of displayed measure is blinking ALARM MEMORY see alarm paragraph IF PROBLEMS PERSIST AFTER ALL ABOVE MENTIONED SOLUTIONS SWITCH OFF THE REGULATOR FOR AT LEAST...

Страница 16: ...d suffer internal damage which may be dangerous Before connect the equipment check the data card this has to be in conformity with the power electric network the plate is located on the back of the P F Regulator This equipment will be assigned only to the use for which it has been specifically made Each other use has to be considered improper and therefore dangerous In order for the correct functi...

Страница 17: ...conducteur 0 018 pour le cuivre L longueur câble de connexion du circuit du T I mt S section du câble de connexion du circuit du T I I courant maximum sur le secondaire du T I 0 08 résistance intérieure du régulateur électronique Si on a des charges inductives monophasées système triphasé déséquilibré brancher le T I sur la phase du réseau qui nécessite le plus de rephasage cosϕ plus bas plus gran...

Страница 18: ... de 1A 3 2 FIXATION MECANIQUE le régulateur est prévu pour le montage sur panneau 138x138 mm utilisant les accessoires appropriés qui sont fournis avec 3 3 PUISSANCE DES BATTERIES Pour un fonctionnement correct de l installation les batteries doivent être a Tout égales entre elles ex 1 1 1 1 1 1 b Une moitié de la suivante ex 1 2 4 8 16 32 c Partie égale parties double des précédentes ex 1 1 2 2 4...

Страница 19: ...y a la possibilité de visualiser sur l afficheur numérique la valeur du cosinusϕ la tension du réseau le courant du secondaire du T I et uniquement sur MPR8 la valeur de la température Lorsque vous mettez en marche le régulateur il est possible de lire la valeur du cosinusϕ 6 REGLAGE DE BASE Lorsque vous mettez sous tension pour la première fois le régulateur doit être programmé en réglant la capa...

Страница 20: ...cosinusϕ En appuyant sur la touche ou _ vous allez afficher la valeur choisie sur le display Nous recommandons de choisir la valeur 0 97 Les valeurs capacitives du cosϕ ϕ ϕ ϕ sont indiquées sur l écran par le symbole précédent la mesure es 95 Le régulateur est étalonné à l usine C K d 0 3 et cosϕ 0 97 N B Grâce à cette préparation on trouve la condition adéquate pour le rephasage lorsque le cosinu...

Страница 21: ...A l arrête des anomalies le régulateur reprend un fonctionnement normal Courant Nul Io Un courant nul circulant sur le circuit ampèremétrique secondaire du T I provoque cette l alarme Celle ci entraîne la visualisation automatique de la mesure du courant avec symbolisation ou la mesure du cosinusϕ avec symbolisation E EE et la visualisation de la condition de charge capacitive limite le fonctionne...

Страница 22: ...ez le branchement du 0Vac sur les bobines du contacteur c Vérifiez le branchement du 220Vac sur la borne C d Vérifiez le bon fonctionnement des contacteurs Visualisation CAP sue l écran a Ligne capacitive sur la ligne d installation du T I b Le T I est sur une mauvaise phase branchez le T I sur la phase R voir 2 et 3 1 c Cosinusϕ ϕ ϕ ϕ de ligne inférieur aux valeurs 0 15 en inductif ou capacitif v...

Страница 23: ...érique Une éventuelle intervention devra être effectuée par du personnel accrédité par COMAR GARANTIE La Société COMAR Condensatori garantie ses propres produits pour une période de 12 mois depuis la date d acquisition La garantie couvre les défauts éventuels de fabrication du matériel et s entend pour une réparation rendue FRANCO dans nos ateliers Au moment de la mise en service les instructions ...

Страница 24: ...08 resistencia interna del regolador electrónico En presencia de carga inductiva monofasica red trifasica desequilibrada montar el TA sobre la fase de la red con mayor necesidad de compensación cos fi mas bajo mayor absorción de corriente eléctrica El cable del secundario del TA deberá ser al menos de sección par de 2 5 mm 2 El conexionado del TA no debe ser protegido por fusible o interruptor con...

Страница 25: ...montaje en el panel plantilla de perforación 138x138 mm por medio de los accesorios suministrados con el equipo 3 3 POTENCIA DE LOS ESCALONES El regulador basa el propio funcionamiento sobre la lógica binaria por lo que la inserción y desinsercion de los escalones se obtiene en sucesión numérica partiendo del primero Para un correcto funcionamiento de la instalación los escalones debe ser dimensio...

Страница 26: ...si es por razones de seguridad el automático vuelve a la condición de reposo Cuando la alimentación se restablece el regulador vuelve a su funcionamiento standard automático 5 INDICADOR DIGITAL Es posible visualizar en sucesión el valor de COS FI TENSIÓN INTENSIDAD de la red de alimentación en el punto donde esta insertado el T A para obtener el efectivo valor de la corriente de linea es necesario...

Страница 27: ... mas el botón Select se enciende el led rojo PF y se accede a la programación del Cos Fi sobre el display se visualiza un numero de tres cifras Dejar el pulsador Ajustar al coseno de Fi deseado mediante incremento o _ decremento Se aconseja de ajustar a mínimo 0 95 mejor 1 00 N B El valor de cos fi CAPACITIVO se visualiza con el signo antes de la medida ej 95 Ejemplo C K impuesto 0 3 cos FI impues...

Страница 28: ...ma de min corriente el regulador se habilita solo la desinsercion de los escalones solo en caso de sobrecompensacion capacitiva Al cesar la condición anormal el regulador volverá al normal funcionamiento Corriente inferior a 10 mA Tal estado no perjudica la normal función MANUAL del regulador pero determina una visualización de la medida de corriente con simbologia y el relativo led intermitente y...

Страница 29: ... 0 sobre la bobina del contactor c Verificar el conexionado a 220 v sobre el borne C d Verificar el correcto funcionamiento del contactor Visualización Letras CAP sobre el display a Línea capacitiva en el punto de instalación del TA b TA sobre la fase equivocada conectar sobre la fase R c Alarma de corriente NULA verificar el conexionado del TA Visualización letra EEE sobre el display Alarma de CO...

Страница 30: ...do golpes violentos puede recibir daño aunque no sea visible y resultar peligroso Antes de conectarlo el aparato cerciorarse que los datos de la placa sean los correspondientes a los de la red de distribución eléctrica la etiqueta de aluminio esta situada a la derecha del equipo Que este aparato deberá ser destinado solo al uso para al cual ha estado expresamente concebido Cualquier otro uso ha de...

Страница 31: ...31 COMAR CONDENSATORI S p A Via del Lavoro 80 40056 CRESPELLANO Bologna ITALY 39 051 733 383 Fax 39 051 733 620 P O BOX 150 40011 ANZOLA EMILIA Bologna ITALY ...

Отзывы: