ComAp,a.s.
Kundratka 2359/17
180 00, Praha 8
Czech Republic
InteliNano-NT MRS, SW version 1.5,
©ComAp – September 2013 1
InteliNano-NT-MRS-1.5-Fast User Guide.pdf
CAN INTERFACE
GENERATOR VOLTAGE
MEASUREMENT
T16 = Neutral
T17 = Phase 1
T18 = Phase 2
T19 = Phase 3
USB interface
L
COM
H
INTPUT TERMINALS
T10 = COM for analog inputs
T11 = binary input
T12 = binary input
T13 = binary/analog input – Low Fuel Level
T14 = binary/analog input – Coolan Temperature
T15 = binary/analog input – Oil Pressure
OUTPUT TERMINALS
T04 = binary output – Starter (6A)
T05 = binary output - Fuel Solenoid (6A)
T06 = binary output (500 mA)
T07 = binary input/output (500 mA)
POWER SUPPLY, D+
T01 = BATT -
T02 = D+
T03 = BATT +
G
ECU
DIESEL / GASOLINE ENGINE
GENERATOR
LOAD
Fu
e
l S
o
le
n
o
id
B
at
te
ry
Sa
rt
e
r
Fu
e
l L
e
ve
l A
n
alo
g
C
o
o
la
n
t T
e
m
p
e
ra
tu
re
A
n
alo
g
O
il P
re
ss
u
re
A
n
alo
g
D+
-
+
A
la
rm
R
e
ad
y T
o
L
o
ad
Fu
e
l S
o
le
n
o
id
St
ar
te
r
C
O
M
R
e
m
o
te
S
ta
rt
A
n
d
L
o
ad
Em
e
rg
e
n
cy
S
to
p
C
A
N
L C
O
M
H
U
SB
B
at
te
ry
+
B
at
te
ry
-
D
+
PC
L1
L2
L3
N
InteliNano NT
MRS
Fast User Guide
Typical wiring diagram
Accessing the setup mode
Ensure the engine is stopped and the controller is in Manual mode (green LED above button
Auto
is turned off).
If you have not configured the custom initialization (init) screen then press and hold
Stop
button, then briefly press
▲
button
and then
Auto
.
If you have already created your own init screen then press and hold
Stop
button and then briefly press
▲
, the custom init screen will appear, keep holding the
Stop
button. Then press
▼
to switch LCD to default init screen, and then press
Auto
.
To move up and down in the setup menu use
▲
and
▼
buttons. Press
Start
button to select or
Stop
button for exit.
Basic settings
Input settings
Engine parameters and protections
ECU setting
Generator protections
Info
Output settings
Outputs and inputs
Output
code
Output source
Type
Terminal assignment
O00
Not Used
binary T04, T05, T06, T07
O01
Starter
binary T04
O02
Fuel Solenoid
binary T04, T05, T06, T07
O03
Stop Solenoid
binary T04, T05, T06, T07
O04
Alarm
binary T04, T05, T06, T07
O07
Ready To Load
binary T04, T05, T06, T07
O08
Prestart
binary T04, T05, T06, T07
O09
ECU Power Relay
binary T04, T05, T06, T07
O10
Choke
binary T04, T05, T06, T07
O11
Glow Plugs
binary T04, T05, T06, T07
Normally Open Contact – output
Normally Open Contact - input
button
Normally Closed Contact – output
Normally Closed Contact
– input
button
User curves
I21
I23
I25
VDO Level %
VDO 5 Bar
VDO 40-
120 °C
Datcon Level %
VDO 10 Bar
VDO 50-
150 °C
Datcon 5 Bar
Datcon High °C
Datcon 7 Bar
Datcon Low °C
Datcon 10 Bar
Not selected
Not selected
Not selected
Input
code
Input source
Type
Terminal assignment
I00
Not Used
binary T07, T11, T12, T13, T14, T15
I01
Emergency Stop
binary T07, T11, T12, T13, T14, T15
I02
Remote Start/Stop
binary T11
I03
Remote Start And Load
binary T11
I04
Access Lock
binary T07, T11, T12, T13, T14, T15
I07
GCB Feedback
binary T07, T11, T12, T13, T14, T15
I10
External Warning 1
binary T07, T11, T12, T13, T14, T15
I11
External Warning 2
binary T07, T11, T12, T13, T14, T15
I12
External Warning 3
binary T07, T11, T12, T13, T14, T15
I13
External Shutdown 1
binary T07, T11, T12, T13,T14, T15
I14
External Shutdown 2
binary T07, T11, T12, T13, T14, T15
I15
External Shutdown 3
binary T07, T11, T12, T13, T14, T15
I20
Low Fuel Level
binary T07, T11, T12, T13, T14, T15
I21
Fuel Level Analog
analog T13, T14, T15
I22
Low Oil Pressure
binary T07, T11, T12, T13, T14, T15
I23
Oil Pressure Analog
analog T13, T14, T15
I24
High Coolant Temperature
binary T07, T11, T12, T13, T14, T15
I25
Coolant Temperature Analog
analog T13, T14, T15
I29
Fuel Level SD
Binary T07, T11, T12, T13, T14, T15
Dimensions
Case dimensions:
118mm x108mm x 40mm
Panel Cutout: 96mm x 96mm
W
ARNING
!
If D+ is not used, connect this terminal to battery positive!