InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
279
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 1 (in % of nominal system frequency given by setpoints
and
Nom frq offset
). When the frequency exceeds this level for more than
time the next load shedding output is opened.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.18
Setpoint: LdRecon f lvl2
Group
Load shedding
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 2 (in % of nominal system frequency given by setpoints
and
Nom frq offset
). When the frequency exceeds this level for more than
time the next load shedding output is opened.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.19
Setpoint: LdRecon f lvl3
Group
Load shedding
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative frequency level for load shedding
stage 3 (in % of nominal system frequency given by setpoints
and
Nom frq offset
). When the frequency exceeds this level for more than
time the next load shedding output is opened.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...