11.2.2.16
Setpoint: Nominal Freq
Group
Basic Settings
Range [units]
50 Hz, 60 Hz [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint adjusts nominal system frequency (choose 50 Hz or 60 Hz).
Setpoint
Nom frq offset
is used for setting offset to the chosen nominal
frequency (-2 to +2 Hz with step 0.01 Hz). Controller regulates to the
Nom frq offset
frequency.
Nom frq offset
is used as 100% for frequency
protections.
11.2.2.17
Setpoint: ControllerMode
Group
Basic settings
Range [units]
OFF, MAN, AUT [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint can be used to select the controller mode. It is equivalent to
selecting the mode by the buttons on the front panel or IntelliVision. Currently
active mode is displayed on the controller main screen.
N
OTE
:
If any of the mode forcing inputs
or
Remote TEST
is active, then the currenly active mode can be different
than the mode selected by the setpoint (resp. panel buttons).
OFF
IM-NT does not influence gen-set group in this mode.
If Mains is healthy and no mains alarm is active, MCB is
closed after
MCB stays closed all the time, regardless of the Mains
condition.
In MCB application - if the controller is switched to OFF
mode while the gen-sets are running and there is
voltage on the bus, MCB is not closed before bus
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...