InteliLite 4 AMF20+AMF25 Operator Guide 

3

 

 

 

 

FAULT  RESET 

button.  Use  this  button  to  acknowledge  alarms  and 

deactivate  the  horn  output.  Inactive  alarms  will  disappearimmediately 
and  status  of  active  alarms  will  be  changed  to  "confirmed"  so  they  will 
disappear as soon as theirreasons dismiss.

 

 

 

UP 

button. Use this button to move up orincrease value.

 

 

 

PAGE 

button. Use this button to switch overdisplay pages.

 

 

 

DOWN 

button. Use this button to move down ordecrease value.

 

 

 

ENTER 

button. Use this button to finish editing a setpoint ormoving right in 

the history page.

 

 

 

START 

button. Works in MAN mode only. Press this button to initiate the 

start sequence of the engine.

 

 

 

STOP 

button. Works  in  MAN  mode  only.  Press  this  button  to  initiate  the 

stop  sequence  of  the  Gen-set.  Repeated  pressing  of  button  will  cancel 
current  phase  of  stop  sequence  (like  cooling)and  next  phase  will 
continue.

 

 

 

GCB 

button. Works in MAN mode only. Press this button to open orclose 

the GCB.

 

 

 

MCB 

button. Works in MAN mode only. Press this button to open orclose 

the MCB.

 

Indicators and others

 

Position

 

Description

 

 

GENERATOR 

status indicator. There are two states 

– Gen-set OK (indicatoris 

green)and Gen-set failure (indicatoris red). Green LED is on if the generatorvoltage and 
frequency is present and within limits. Red LED starts flashing when Gen-set failure 
occurs. After FAULT RESET button is pressed, Red LED goes to steady light (if an 
alarm is still active) oris off (if no alarm is active).

 

 

MAINS 

status  indicator.  There  are  two  states 

–  Mains  OK  (indicatoris  green)and 

Mains failure (indicatoris red). Green LED is on, if mains is present and within limits. 
Red LED starts blinking when the mains failure is detected and afterthe Gen-set has 
started  and  connected  to  the  load  it  lights  permanently  until  the  mains  failure 
disappears.

 

 

Graphic B/W display, 132 × 64 px.

 

Содержание InteliLite4 AMF20

Страница 1: ...ght 2021 ComAp a s Written by Jan Liptak Prague Czech Republic ComAp a s U Uranie 1612 14a 170 00 Prague 7 Czech Republic Tel 420 246 012 111 E mail info comap control com www comap Operator Guide control com ...

Страница 2: ...ill not change the mode if the controller mode is forced by one of binary inputs listed in the Reference Guide Operating modes chapter RIGHT button Use this button to move right orto change the mode The button can change the mode only if the main screen with the indicatorof currently selected mode is displayed Note This button will not change the mode if the controller mode is forced by one of bin...

Страница 3: ...ase of stop sequence like cooling and next phase will continue GCB button Works in MAN mode only Press this button to open orclose the GCB MCB button Works in MAN mode only Press this button to open orclose the MCB Indicators and others Position Description GENERATOR status indicator There are two states Gen set OK indicatoris green and Gen set failure indicatoris red Green LED is on if the genera...

Страница 4: ... case the generatorstatus indicatoris ok LOAD Green LED is ON if load is supplied by mains orby generator It means that Genset ormains is OK and propercircuit breakeris closed MCB Status Consists of 3 green LEDs The middle green LED is on if MCB is closed It is driven by MCB CLOSE OPEN output orby MCB feedback signal Side green LEDs are on in case the mains status indicatoris ok 6 back to Front pa...

Страница 5: ...screen The page Setpoints contains all setpoints organized to groups and also a special group forentering password The page History log shows the history log in the orderthat the last record is displayed first 2 1 Main Screen 2 1 1 Symbols Padlock active when LBI ACCESS LOCK is active R active when there is active remote connection to controller Exclamation mark active when there is any alarm in a...

Страница 6: ...te Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 7: ...AMF20 AMF25 Operator Guide 7 Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 8: ...AMF20 AMF25 Operator Guide 8 Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 9: ...n measurement pages Note Available only with plug in module Note Use Up and Down button to move between measurement pages Note Available only with plug in module Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages ...

Страница 10: ...button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Use Up and Down button to move between measurement pages Note Available only with plug in module ...

Страница 11: ... plug in module Note Use Up and Down button to move between measurement pages Note Available only with plug in module Note Use Up and Down button to move between measurement pages Note Available only with plug in module Note Use Up and Down button to move between measurement pages Note Available only with ECU supported by TIER4F ...

Страница 12: ...itional screens and also some screens can be hidden Screen s visibility depends on actual configuration usage of extension or communication modules ECU etc 2 3 Setpoint Screens Note From all measurement pages we can fluently go to the setpoint group page by pressing Page button Note Use Up and Down button to select required setpoint group Note Use Enter button to enter selected setpoint group Note...

Страница 13: ...InteliLite 4 AMF20 AMF25 Operator Guide 13 Note Use Enter button to enter selected setpoint ...

Страница 14: ...tpoint Note Use Enter button to confirm adjusted value of setpoint Note Use Page button to discard changes to set setpoint to previous value and to return to the list of setpoints of selected group 2 4 History Log Note From all measurement pages we can fluently go to the setpoint group page by pressing Page button ...

Страница 15: ... to the history log pages by pressing Page button Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log ...

Страница 16: ...Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log ...

Страница 17: ...Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the next page of history log ...

Страница 18: ...arm reason Note Use Enter button to move to the next page of history log Note Use Up and Down button to select required alarm reason Note Use Enter button to move to the first page of history log IMPORTANT The records are numbered in reverse order i e the latest newest record is 0 and older records have 1 2 etc Note This is only basic history record There can be some additional screens in case tha...

Страница 19: ...ity reasons following useraccess Active alarmsaredisplayedas white text on black background It means the alarmis still active i e the appropriatealarmconditions arestill present Inactive alarmsaredisplayed as black text on white background It meansthe alarmis no moreactive i e the appropriatealarmconditions aregone Not confirmedalarms aredisplayedwith an asterisk It means the alarmis still not ack...

Страница 20: ...ation module is plugged in the controller The purpose of alarm is to inform that the controllermight be oris connected to the untrusted interface and cybersecurity rules are not fulfilled due to default administratorpassword Wrn Password reset e mail addr is not setappears in alarmlist when there is no email address set and the administratorpassword is not the default one The purpose of alarm is t...

Страница 21: ...ement pages we can fluently go to the setpoint group page by pressing Page button Note Use Up and Down button to select setpoint group Login Note Use Enter button to enter setpoint group Login Note Use Up and Down Button to select Login Note Use Enter button to enter Login ...

Страница 22: ... Button to change the digit Note Use Left and Right button to move between digits Note Use Enter button to confirm the UserID or Page button to cancel entering Login PIN Edit Note Use Up and Down Button to change the digit Note Use Left and Right button to move between digits ...

Страница 23: ...situation The detailed behaviorof the controllerdepends on situation 4 1 1 PIN protection If an userperforms ten consecutive attempts to login using UID PIN providing correct UID but incorrect PIN the useraccount is permanently blocked forlogin using UID PIN The usermust login with username password and change the PIN to unblock this login method again 4 2 Reset accounts to factory default If cred...

Страница 24: ...t group page by pressing Page button Note Use Up and Down button to select setpoint group Login Note Use Enter button to enter setpoint group Login Note Use Up and Down Button to select Login Note Use Enter button to enter Login Note Use wrong credentials wrong UserID or PIN Note Use Enter button to accept the inputs ...

Страница 25: ...InteliLite 4 AMF20 AMF25 Operator Guide 25 Note Use Page button to return to the Main screen 6 back to Logout ...

Страница 26: ...ode Note From all measurement pages we can fluently go to the setpoint group page by pressing Page button Note Use Enter button to enter setpoint group Login Note Use Up and Down Button to select Production Mode Note Use Enter button to enter Production Mode ...

Страница 27: ...abled is confirmed by Enter button the option Enabled is no longer on the screen and therefore it is not possible to enable Production mode by HMI display screen Use InteliConfig to enable the Production mode 6 back to Production mode 7 Information screen Note On Main measurement screen press Enter and Page button together Enter button has to be pressed first ...

Страница 28: ... 4 AMF20 AMF25 Operator Guide 28 Note Use Page button to move to the next page Note Use Page button to move to the next page Note Use Up button to move back to main measurement screen 6 back to Information screen ...

Страница 29: ... selection Note On Main measurement screen press Enter and Page button together Enter button has to be pressed first Note Use Page button to move to the next page Note Use Page button to move to the next page Note Use Page button to move to the next page ...

Страница 30: ...InteliLite 4 AMF20 AMF25 Operator Guide 30 Note Use Up and down button to select required language Note Use Enter button to confirm selected language 6 back to Language selection ...

Страница 31: ...nt Note On any measurement screen press Enter and Up button together for higher contrast Note On any measurement screen press Enter and Down button together for lower contrast Note After setting a contrast no another action is needed 6 back to Display contrast adjustment ...

Отзывы: