background image

 
Step 5:

 

Select the correct controller address and confirm COM1 mode is set to Direct. 

 

 

This can be found by pressing page> Comms Settings on the front screen of the controller. *If you 
have a controller with old firmware, this will be found under basic settings.  

 

If COM1 mode needs to be changed, press enter and use the arrows to select direct. If there is an * 
before the setpoint like shown below, the password must be entered first. This can be done by 
pressing page and selecting password.  

 

 

 

 

 

 

 

Step 6:

 

Confirm you are connected! 

 

 

This is done by seeing a green status bar and Dde server: Running status at the bottom 
of LiteEdit

 

 

 

 
 
 

 

 

 

 

Содержание InteliLite NT MRS19

Страница 1: ...uals 2 How to Connect and Save the Archive 3 Procedure for Replacing a Controller 4 Upgrading Controller Firmware 5 FAQ s a What does FLS stand for b What does Wrn RA15 Fail mean c What does Wrn Maintenance mean A short video has been created to briefly introduce you to configuring your controller using LiteEdit This contains information on how to configure inputs outputs sensors extension modules...

Страница 2: ...l provide you with the LiteEdit software needed to program your controller Step 3 Expand manuals and download the InteliLite NT MRS 2 2 Reference Guide This is the main manual for the controller If Interfacing with an ECU Expand manuals and download the Electronic Engines Support Guide This will help you properly establish communication with the ECU If setting up Modbus Remote Connection Internet ...

Страница 3: ...adapter for the first time Confirm the driver is correctly installed by double clicking on the adapter shown in the picture below Step 2 Connect your computer to the controller Power on the controller Open LiteEdit Step 3 Open a Direct Connection Step 4 Select the COM port of your computer that the adapter is plugged into This can be confirmed by viewing your ports in device manager shown below Do...

Страница 4: ...d firmware this will be found under basic settings If COM1 mode needs to be changed press enter and use the arrows to select direct If there is an before the setpoint like shown below the password must be entered first This can be done by pressing page and selecting password Step 6 Confirm you are connected This is done by seeing a green status bar and Dde server Running status at the bottom of Li...

Страница 5: ...ctly installed and no pins are damaged on the circuit board If viewing the controller from rear module must be on right side Confirm your 9 pin serial cable is a Null Modem they are not all the same Null modem means pins 2 and 3 are swapped and not straight through You can verify this by testing continuity if need be Confirm all connects are solid and cables in good condition ...

Страница 6: ... want to pull program from old controller and load it into the new one These can also be used if you want to make a copy of another controller Step 1 Connect to old controller and save the archive in an easy to find location Step 2 Right click on that saved archive make a copy and paste it in same location As seen below ...

Страница 7: ...roller values IL info Take note of the new controller FW version You will need this information Below is an example of controller with FW 2 2 Step 5 Select controller programming and cloning archive configuration upgrade A new window will pop up shown below ...

Страница 8: ...t archive and select the same firmware version as your new controller Step 8 Make sure the output directory is in the same location as the copy archive shown below is steps 6 8 completed Step 9 Continue to press next and when asked if you want to overwrite the existing copy archive select Yes to All shown below ...

Страница 9: ...o you know it has been updated shown below You can also open this file offline to confirm the archive did indeed upgrade to the newer FW version Step 11 Connect to the new controller Step 12 Press the select configuration icon from the top task bar shown below and select the archive you have just updated and renamed ...

Страница 10: ...shown below You will be asked if you want to overwrite setpoints by values from the selected archive press Yes Your controller is now programmed Please take the time to verify all setpoints and configuration has transferred properly There can sometimes be errors when a large firmware change is taking place There can also be errors when the updated firmware version has new setpoints features that w...

Страница 11: ...Upgrading Controller Firmware Step 1 Connect to controller and enter your password Step 2 Select Controller Programming and Cloning Programming shown below ...

Страница 12: ...s outputs ECU Extension modules ect with what is in a default archive Make sure your existing one is saved Step 4 You will be asked if you want to overwrite setpoints by values from the default archive This is up to you If you select no setpoints will remain the same as currently in controller Your controller firmware has been programmed ...

Страница 13: ...ou communication has been lost with this device Next Steps Confirm proper Can wiring and installation of the terminating resistors More information can be found in the RA15 Reference Guide or IL NT Communication Guide Don t have a RA15 Connect with LiteEdit Open configuration and select the RA15 icon from the too task bar This is where you can select the RA15 as not being connected C What does Wrn...

Страница 14: ......