InteliLite
NT
– AMF20/25, SW version 2.2, ©ComAp – September 2014 73
IL-NT-AMF-2.2-Reference Guide.pdf
Engine Params
Starting RPM
[%]
“Firing” speed when IL controller stops cranking (starter goes OFF).
Step:
1% of nominal RPM
Range:
5
– 50 %
Starting Oil P
[Bar]
When reached controller stops cranking (starter goes OFF).
Step:
0,1 bar
Range:
0,0
– 10,0
Hint:
There are three conditions for stop cranking: RPM >
Starting RPM
, Oil Pressure >
Starting Oil P
and
D+ (when enabled) => 80% of battery voltage. Starter goes off when any of these conditions is valid.
Prestart Time
[s]
Time of closing of the
Prestart
output prior to the engine start.
Set to zero if you want to leave the output
Prestart
open.
Step:
1s
Range:
0
– 600 s
MaxCrank Time
[s]
Maximum time limit of cranking.
Step:
1s
Range:
1
– 255 s
CrnkFail Pause
[s]
Pause between Crank Attempts.
Step:
1s
Range:
5
– 60 s
Crank Attempts
[-]
Max number of Crank Attempts.
Step:
1
Range:
1
– 10
Idle Time
[s]
Idle time delay starts when RPM exceeds
Starting RPM
. Start fail is detected when during Idle state
RPM decreases below 2.
During the
Idle time
timer running the binary output
Idle/Nominal
is opened when it elapses the
Idle/Nominal
output closes. Binary output
Idle/Nominal
opens during Cooling period again.
Step:
1 s
Range:
0
– 600 s