InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008
72
IL-NT-AMF-Reference Guide1.2.pdf
History file
InteliLite NT stores a record of each important event into the history file. The history file seats 117
records. When the history file is full, the oldest records are removed.
Hint
:
To force history download in LiteEdit (direct,,modem or Internet) open History window and select
History | Read history command.
Record structure
Abbreviation
Historical value
Num
Number of historical event
Reason Event
specification
Date
Date of historical event in format DD/MM/YY
Time
Time of historical event in format HH:MM:SS
RPM Engine
speed
Pwr
Generator active power
PF Generator
PF
LChr
Character of the load
Gfrq Generator
frequency
Vg1
Generator voltage L1
Vg2
Generator voltage L2
Vg3
Generator voltage L3
Ig1
Generator current L1
Ig2
Generator current L2
Ig3
Generator current L3
Mfrq Mains
frequency
Vg1
Mains voltage L1
Vg2
Mains voltage L2
Vg3
Mains voltage L3
V Battery
Battery voltage
OilP
IL-NT Analog input 1 value ( default Oil pressure)
EngT
IL-NT Analog input 2 value ( default Water temperature)
FLvl
IL-NT Analog input 3 value ( default Fuel level)
AIM1
IG-IOM, IGS-PTM Analog input 1 value (when configured IG-IOM, IGS-PTM)
AIM2
IG-IOM, IGS-PTM Analog input 2 value (when configured IG-IOM, IGS-PTM)
AIM3
IG-IOM, IGS-PTM Analog input 3 value (when configured IG-IOM, IGS-PTM)
AIM4
IG-IOM, IGS-PTM Analog input 4 value (when configured IG-IOM, IGS-PTM)
BINARY
INPUTS
Binary inputs IL-NT
BIM
IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM, IGS-PTM)
BINARY
OUTPUTS
Binary outputs IL-NT
BOM
IG-IOM, IGS-PTM Binary outputs (when configured IG-IOM, IGS-PTM)
FC
ECU alarm FailureCode
FMI
ECUalarm Failure Mode Identifier