InteliLite 9 Global Guide
28
ConnectionType: Split Phase
Image 4.8 Split phase application
IMPORTANT: The second phase of split phase connection is connected to the terminal, where is
normally connected the third phase.
ConnectionType: Mono Phase
Image 4.9 Mono phase application
Voltage measurement MRS wiring
There are 4 voltage measurement Connection Type (setpoint
[3Ph4Wire /3Ph3Wire
/ Split Ph / Mono Ph]) options, every type matches to corresponding generator connection type.
Note:
For fusing of voltage measurement input use T1A or T2A fuse.
The generator protections are evaluated from different voltages based on
setting:
3Ph 4W – Ph-Ph voltage, Ph-N voltage
3Ph 3W – Ph-Ph voltage