3 Applications overview
3.1 AMF - Automatic Mains Failure Start
3.1 AMF - Automatic Mains Failure Start
The typical scheme of Automatic Mains Failure Start application is shown below. The controller controls two
breakers – a mains breaker and a generator breaker. Feedback from both breakers isn’t necessary. InteliLite
controllers can also work without breaker feedbacks.
Image 3.1 AMF application overview
3.2 MRS - Manual Remote Start
The typical scheme of Manual Remote Start application is shown below. The controller controls one breaker – a
generator breaker. Feedback from breaker isn’t necessary. InteliLite controllers can also work without breaker
feedback.