ID-Mobile Global Guide
78
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 10 [Bar]
Default value
10
Step
Comm object
9681
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Oil pressure limit when controller stops cranking = one of the engine running indications. To activate this
function any Analog input must be configured to Analog logical input
Note:
Step, Range and dimension depend on corresponding Analog input sensor characteristic.
Starting POil
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 10.00 [bar]
Default value
10
Step
0.01 bar
Comm object
10138
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Coolant pressure limit = one of the engine running indications. To activate this function any Analog input
must be configured to Analog logical input
Note:
Step, Range and dimension depend on corresponding Analog input sensor characteristic.
StartPCoolant (AS only)