ID-Mobile Global Guide
68
Setpoint group
Basic settings
Related FW
2.6.0
Range [units]
[ISOCHRON, DROOP, BIN.INPUT]
Default value
ISOCHRON
Step
Comm object
10230
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Activates/deactivates the logical binary output DROOP Sw, that can be configured as J1939 output to
switch ECU mode.
BIN.INPUT: ISOCH/DROOP mode is switched via Binary input BI DROOP (DROOP when closed).
Governor Mode
Setpoint group
Basic settings
Related FW
2.6.0
Range [units]
[IDLE, NOMINAL, BIN.INPUT]
Default value
IDLE
Step
Comm object
10336
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Activates/deactivates the logical binary output NOMINAL Sw, that can be configured as J1939 output to
switch ECU.
BIN.INPUT: IDLE/NOMINAL mode is switched via Binary input BI NOMINAL (NOMINAL when closed).
Idle/Nominal